Configuration
Entek IRD 6652 DSP Protection Monitor
19
Note:
In order for these options to be active, you must do the following:
l
Set the MON ECC option to +RELAY or -RELAY in the ECCNTRY submenu under
the Factory menu (page 30). If you set MON ECC to DISABLE, the 6652 DSP does not
perform vector monitoring.
l
Set TACHO to YES in the TX OK submenu under the Factory menu (page 30).
l
Connect a 1x tachometer input signal to the 6652 DSP monitor.
For more information on the 6652 DSP and vector monitoring, see “Understanding Vector
Monitoring” on page 36.
VALID ORDER NOT AVAIL message
If you see the “VALID ORDER NOT AVAIL” message when you press
SEL
to select
CURR 1 or CURR 2 for the CAP REF option, it means that the monitor cannot detect a
valid reference on the selected channel. The monitor then resets CAP REF to NO.
Factory Menu Configuration
The Factory menu allows you to set the following:
l
MODBUS communication options
l
Input configuration, including speed bands for alarm inhibit or multiply, transducer
units, display units, high pass filter, low pass filter, and vector monitoring
l
Transducer normal OK limits, tachometer on/off and offset
l
Relay operation
l
Number of channels
l
Analysis function, including trends, spectra, orbits, windowing, averaging, transient
monitoring, and runout
The controls to access the Factory menu and configure the 6652 DSP monitor are all on the
front panel of the monitor. See “Front Panel Description” on page 3 for a diagram of the
front of the monitor.
Note:
Some of these functions, including many on the ANALYSIS menu, may not yet be available
with the 6652 DSP monitor. Contact Entek IRD for more information on the latest available
features for the 6652 DSP.