Installation and Operation Manual - COMTEC
®
6000
Technical Data
Doc.-ID: COM6000_11022020_EN
49
A
Technical Data
A.1
Technical Specifications - Electronic Unit
Housing:
sheet steel powder coated;
RAL6029 (GRP version optional)
(SME-54, 19” rack optional)
IP Code:
Safe Area Housing: IP66
GRP cabinet: IP66
19“ housing: IP20
Display:
LC Dot Matrix 240 x 64 - LED backlit
Keypad:
membrane keypad
Signal LEDs:
orange: alarm, orange: maintenance, red: error
O
2
measuring range:
2 ranges, freely configurable from 0-2 % O
2
to 0-25 % O
2
(other O
2
measuring ranges on request)
Accuracy O
2
:
< 0.5 % of measured value or 0.02 Vol % O2 (higher value valid)
CO
e
measuring range:
1 range, min.: 0-1000 ppm / max.: 0-5000 ppm
(factory adjustable, other ranges on request)
Accuracy CO
e
:
5 % of range end
Mains Voltage
:
115 VAC ±10 % 50 to 60 Hz
230 VAC ±10 % 50 to 60 Hz
Power consumption:
225 VA (typical measuring mode)
425 VA (heating phase)
Recommended fuse:
10 A
Output signal:
O
2
- active, 0/4 to 20 mA max.
load 500
Ω
CO
e
- active, 4 to 20 mA max.
load 500
Ω
Relay contact:
24 V AC/DC, 1 A
Relay contact solenoid valve:
230 V AC/DC, 1 A
Dimensions:
300 x 440 x 240 mm (W x H x D) (standard field housing)
483 x 177 x 400 mm (W x H x D) (19" rack)
Weight:
approx. 20 kg
approx. 12 kg (19” rack)
Temperature range - storage: *
-40 °C to +80 °C (-40 °F to 176 °F)
Temperature range - operation: *
-20 °C to +55 °C (-4 °F to 129 °F); others on request
* Other temperature ranges on request