Rope Fluid Leak Sensor Installation Instructions
EA9112
Note: The wire mount, shown here, is for installation on the
floor or ground surface. This MUST be used in the detection
area.
If mounting to a cabinet or wall, use the adhesive-backed
mount (provided). The adhesive-backed mount in the
detection area may prevent or delay leakage notification.
1. Connect the RJ-45 jack on the Rope Fluid Leak Sensor assembly to a sensor port on the Enlogic PDU, Inline Energy
Meter, or Sensor Hub (model EA9106).
2. Thread the Rope Fluid Leak Sensor cable (EW00253) through the rack and along the desired path of detection.
Note: Up to 5 Rope Fluid Leak Sensor Cables can be connected to lengthen the detection zone. These can be
purchased through Enlogic.
3. Secure the Rope Fluid Leak Sensor cable to the rack and ground using the cable ties and/or adhesive mounting
strips provided.
Detecting Environmental Sensors
The sensor serial number is listed in the Enlogic Web UI when the sensor is detected. To identify each detected environmental
sensor:
1. Expand the PDU folder to show all components and groups.
2. Select External Sensors to view the External Sensors page the right pane.
3. Confirm that the serial number on the sensor device matches the number in the sensor table.