To setup the PDU with the ability to Ping the server IP/hostname and receive status updates:
1. Go to Device Configuration > Server Reachability.
2. Select New.
3. Enter an IP Address/Hostname. Select the Enable Ping Monitoring checkbox.
4. Change the Number of Successful Pings, Number of Unsuccessful Consecutive Pings, and Wait Time, if desired.
5. Select OK.
6.
(
) To configure the server to send notifications (SMTP Message, SNMP Trap, or both) go to Device
Configuration > Event Rules.
USB
To make the PDU accessible through the USB port on the unit, you must:
1. Go to Device Configuration > USB Settings.
2. Select the Enable USB Access Checkbox.
LDAP Server Settings
To setup LDAP to access the Active Directory (AD) and provide authentication when logging into the PDU via the
Web Interface:
1. Go to Device Configuration > LDAP.
2. Select the LDAP Enable checkbox.
3. Use the drop down menu to chose the Type of LDAP Server. Either Open LDAP or Microsoft Active Directory.
4. Enter an IP Address / Hostname of the domain controller/Active Directory (AD) Server.