Flow switch failure
FL
No water/little water in
water system.
Check the water flow volume,
water pump is failure or not
High pressure protect
HP1
High pressure switch action
Check through each pressure
switch and return circuit
Low pressure protect
LP1
Low pressure switch action
Check through each pressure
switch and return circuit
Exhaust temperature/ or
current protect
tC1
Exhaust temperature or
current is too high
Check through exhaust temp.
switch and current
17.17
Parameters
“µC²SE”
Parameter
Description
Un
Value
BACKUP SISTEM
A08
Backup setpoint
°C
25
A09
Differential A08
°C
5
A16
Backup delay
min
60
COMPRESSOR
C01
Minimum time to the compressor remain active after turn ON,
even if a stop command occurs. Establishes the minimum
activation time of the output, independently from request
s
120
C02
Compressor minimum switch-on time. Establishes the minimum
switch-off time if the output, independently from request
s
180
C03
Compressor minimum switch-off time. Establishes the minimum
time between two successive switch-ons of the same output.
s
300
C07
Delay to start the compressor after turn ON the water pump
s
60
C08
Delay to stop water pump after turn OFF the compressor
min
2
DEFROST
D03
Minimum pressure to initiate the defrost cycle. The defrost cycle
starts only if the pressure remains below D03 during D05 time.
bar
(abs)
2,6
D04
Pressure to stop defrost cycle
bar
(abs)
14
D05
Delay to start defrost cycle
s
120
D06
Minimum time to defrost cycle (0 min)
s
0
D07
Maximum time to defrost cycle
min
10
D08
Delay between defrost cycles.
min
45
D11
Backup system ON during defrost cycle
int
1
D12
Inversion time cycle (before initiating the defrost cycle). During
this period the compressor is off and is inverted the position of
the 4 way valve..
min
1
D13
Inversion time cycle (after defrost cycle). During this period the
compressor is off and is inverted the position of the 4 way valve..
min
1
D16
Fan at maximum speed after defrost cycle
s
30