Heat pumps models
units
FF Evi 10
FF Evi 15
FF Evi 17
HEATING
1)
Heating capacity
kW
9,15
14,61
16,95
Power input
kW
2,28
3,53
3,91
COP
---
4,02
4,13
4,34
COOLING
2)
Cooling capacity
kW
6,2
9,5
12,0
Power input
kW
2,3
3,5
4,5
EER
---
2,7
2,71
2,78
ELECTRICAL HEATER (BACKUP)
Electrical heater
kW
1,5
3,0
3,0
Electrical heater running current
A
6,8
13,5
4,5
Power supply
V~
220/240
220/240
380/420
HEAT PUMP SPECIFICATIONS DATA
Power input
kW
4,0
5,8
6,7
Current input
A
20,2
30
14,4
Max current input (with backup)
A
20,2+6,8
30+13,5
14,4+4,5
Power supply
V
220/240
220/240
380/420
Frequency
Hz
50
50
50
Sound
db(A)
46
50
52
Compressor quantity
---
1
1
1
Compressor type
---
Scroll
Scroll
Scroll
Fan quantity
---
1
2
2
Refrigerant type
---
R407C
R407C
R407C
Refrigerant load
Kg
3,5
5,5
5,5
Hydraulic connections
Inches
1
1
1
Water pressure drop
kPa
17
34
34
Min. flow
m³/h
1,5
2,6
2,8
Net weight
Kg
116
213
205
1) Heating condition (EN14511: 2011):
outdoor temperature DB/WB 7
o
C/6
o
C;
outlet water 35
o
C;
inlet water 30
o
C.
2) Cooling condition (EN14511: 2011):
outdoor temperature DB/WB 35
o
C/24
o
C;
outlet water 7
o
C;
inlet water 12
o
C.