The thermostat cannot be installed:
in exterior walls.
near the radiators, convectors, etc.
behind or near the doors.
near to the windows.
15.12
Electrical wiring
Model
Power source
Max. current
* Power source cable
section
FF Evi 10
220/240V~ /50Hz
27 A
4 mm²
FF Evi 15
220/240V~ /50Hz
43,5 A
6 mm²
FF Evi 17
380/420V~ /50Hz
19 A
2,5 mm²
*
The above wire sizes are
selected at the maximum current of the unit
according to the European Standard EN60335-1 and
considering a cable
length of 10 meters.
NOTE:
Follow local codes and regulations when selecting field wires, circuit
breakers and earth leakage breakers.
Select the main switches according to the next table:
Model
Power source
Max.
current
CB
ELB
(no. poles/A/mA)
FF Evi 10
220/240V~ /50Hz
27 A
32 A
2/32/30
FF Evi 15
220/240V~ /50Hz
43 A
63 A
2/63/30
FF Evi 17
380/420V~ /50Hz
19 A
25 A
4/25/30
CB
– Circuit breaker; ELB – Earth leakage breaker.