Tan
φ
●
Frequency
●
21.5 Trend curves
Quantity
1 sec
AVG
V1, V2, V3
●
●
VGround
●
U12, U23, U31
●
●
I1, I2, I3, In
●
●
P1, P2, P3
●
(1)
Pt
●
●
(1)
Qt
●
St
●
FP1, FP2, FP3
●
(1)
FPt
●
●
(1)
Cos
φ
1, Cos
φ
2, Cos
φ
3, Cos
φ
t
●
(1)
Tan
φ
●
(1)
Frequency
●
V1, V2, V3 peak factor
●
I1, I2, I3 peak factor
●
U unbalance
●
THD V1, V2, V3
●
●
THD U12, U23, U31
●
●
THD I1, I2, I3, In
●
●
Analog input (0 to 8)
●
●
(1) Measured both in generator and receiver mode
21.6 Inherent errors
Conforms to the monitoring standard NF EN 61557-12
A 23°C
±
2°C, 50 Hz (except for the quantity F)
V
nom
/U
nom
= 230 V/400 V for PT secondary > 100 V
V
nom
/U
nom
= 57.7 V/400 V for PT secondary > 100 V
I
nom
= 5A
Quantity
Conditions
0.5s accuracy (1)
0.2s accuracy (2)
V
V between [10% and 120%] of V
nom
±0.5% of the reading
±0.2% of the reading
U
U between [10% and 120%] of U
nom
±0.5% of the reading
±0.2% of the reading
I
I between [5% and 130%] of I
nom
±0.5% of the reading
±0.2% of the reading