U
SER MANUAL
–
ENERIUM
100/200/300
MS1-7352 ENERIUM100/200/300_ Ed04 User Manual
Page 16 / 86
6
R
EAR
V
IEW
This section describes which components are accessible from the rear, for each model:
Rear view of the ENERIUM 100, 200 and 300
Rear view of the ENERIUM 110, 210 and 310
6.1 Measurement inputs
6.1.1 Voltage measurement inputs
6.1.1.1 Location
The voltage input terminals are labelled 9 to 13 on the rear right lower label.
6.1.1.2 Characteristics
Variables
Range
Nominal phase voltage
57.7/230 V
Nominal line voltage
100/400 V
Maximum line voltage
520V
Crest factor
2
Frequency
42.5 Hz to 69 Hz
24-hour overvoltage
800 V
Per-phase consumption
0.1 VA
Impedance
1 M
Ω
No.
Function
1
Optional card connector block (digital or analog)
2
Rear optical interface
3
Current input terminals
4
Voltage input terminals
5
RS485 connector
6
Ethernet connector
7
Auxiliary source connector
Voltage inputs