U
SER MANUAL
–
ENERIUM
100/200/300
MS1-7352 ENERIUM100/200/300_ Ed04 User Manual
Page 73 / 86
Quantity
Conditions
0.5s accuracy (1)
0.2s accuracy (2)
Sin (
φ
) between [0.5 inductive and 0.5
capacitive]
I between [5% and 10%[ of I
nom
I between [10% and 130%] of I
nom
±0.625% of the reading
±0.5% of the reading
±0.25% of the reading
±0.2% of the reading
Sin (
φ
) between [0.25 inductive and
0.25 capacitive]
I between [10% and 130%] of I
nom
±0.625% of the reading
±0.25% of the reading
Apparent E
I between [2% and 5%[ of I
nom
I between [5% and 130%] of I
nom
±1% of the reading
±0.5% of the reading
±1% of the reading
±0.2% of the reading
Harmonics by order
-
±0.5% of the reading
THD
-
±0.5% points
Hour meter (HM)
-
±20 ppm
Time
T = 23°C
±20 ppm (i.e. ± 52 seconds in 30 days)
(1) Only for ENERIUM 100/110/200/210
(2) Only for ENERIUM 200/210/300/310
21.7 Environmental constraints
21.7.1 Climatic constraints
Operating temperature
-10°C to 55°C (K55 in accordance with NF EN 61557-12)
Operating humidity
Up to 95% at 40°C
Storage temperature
-25°C to +70°C
21.7.2 Safety constraints
Pollution level
2
Fire resistance
Conforms to UL94 for safety level V1
Installation category
III
21.7.3 Mechanical constraints
Protection class
To IEC 60529, for the following level of safety:
IP 51 (on the front panel)
IP 20 (on the rear panel)
Mechanical shock
Conforms to IEC 61010-1
Vibration
CEI 60068-2-6 (Method A)
Free fall with packaging
At a height of 1m, in accordance with NF H 0042-1