Operating the ESE 607 / 957 DBG (ES) DIN
Connecting up to consumers
42
ESE 607 / 957 DBG (ES) DIN
Issued: February 2013
4.6
Connecting up to consumers
Proceed as follows to connect up consumers to the generator.
Requirements
The following requirements must be ful
fi
lled:
●
started generator (see 4.4)
●
protective earthing conductor test completed (see 4.7)
●
a switched off consumer
WARNING!
Electric shocks cause injury or death.
●
do not earth the generator (except for special option FI).
●
do not connect protective conductor to an existing potential
equalisation line.
●
do not connect the generator to an existing electrical grid.
Connecting up consumers
You can connect up consumers using Schuko or CEE sockets.
Figure 4-3: Connecting up consumers