6. Align the adapter if necessary.
7. While holding the cable entry with the 24 mm wrench, tighten the fixing nut using the 42 mm
wrench (torque 7 Nm).
4.5
Remote mounting
Remote mounting - where the field device and adapter are mounted at a distance from one another
- can be required in various situations, such as when:
• There is not enough space to mount the adapter on the field device.
• Signal reception at the field device is too weak for correct operation.
• The field device is subject to vibration above the recommended limit.
The WirelessHART Adapter can be mounted on a wall, post or other object using the "wall/pipe
mounting bracket". In this case, the WirelessHART Adapter and the field device are connected via
a connecting cable and cable glands.
The "wall/pipe mounting bracket" and the cable glands are accessories. The connecting cable is not
included in the scope of delivery.