RMA42
Commissioning
Hauser
31
6.4.9
Expert menu
You activate the Expert mode by pressing ‘
E
’
É
‘
Expert
’
The Expert menu offers advanced device settings to be able to adapt the device optimally to the
application conditions.
An access code is needed to access the Expert menu. This code is preset at the factory as "0000". If
a new access code is defined by the user, it replaces the access code assigned at the factory.
The Expert menu is enabled as soon as the correct access code has been entered.
The configuration options which the Expert mode also offers in addition to the parameters of the
normal setup are explained in the following section.
Input
É
Analog input 1/2
Bar 0%, Bar 100%
Change the scaling of the bar graph; default value: channel scaling
Decimal places
Specify the desired number of decimal places; default value: 2 decimal places
Damping
The input signal can be damped by means of a low-pass filter.
The damping is specified in seconds (can be configured in steps of 0.1 seconds, max. 999.9s).
Default values:
Once 5 times the filter time have elapsed, 99% of the actual measured value is reached.
a0010508
Fig. 15:
Signal damping
Analog in: analog input signal
d: set damping
Failure mode
If an error is detected at one of the two inputs, the internal status of the input is set to error. The
behavior of the measured value in the event of an error can be defined here.
•
Invalid = invalid value:
The value is not calculated further since it is passed on as an invalid value.
•
Fixed value = constant value:
A constant value can be entered. This value is used if the device should perform further
calculations. The input continues to be in a fault state. The error flag is also transmitted if the
signal is processed further.
Input type
Default value
Current and voltage inputs
0.0 s
Temperature inputs
1.0 s