RMA42
Technical data
Hauser
41
10
Technical data
10.0.1
Input
Inputs
One or two universal inputs
Measured variable
Current, voltage, resistance, resistance thermometer, thermocouples
Measuring ranges
Current:
• 0/4 to 20 mA +10% overrange
• Short-circuit current: max. 150 mA
• Load: 10
Ω
Voltage:
• 0 to 10 V, 2 to 10 V, 0 to 5 V, 0 to 1 V, 1 to 5 V, ± 1 V ± 10 V, ± 30 V, ± 100 mV
• Max. permitted input voltage:
Voltage
≥
1 V: ± 35 V
Voltage < 1 V: ± 12 V
• Input impedance: > 1 M
Ω
Resistance:
• 30 to 3000
Ω
Resistance thermometer:
• Pt 100 as per IEC60751, GOST, JIS1604
• Pt 500 and Pt 1000 as per IEC60751
• Cu 100, Cu 50, Pt 50, Pt 46, Cu 53 as per GOST
• Ni 100, Ni 1000 as per DIN 43760
Thermocouple types:
• Type J, K, T, N, B, S, R as per IEC60584
• Type U as per DIN 43710
• Type L as per DIN 43710, GOST
• Type C, D as per ASTM E998
Update time
200 ms
Linearization
Linearization of input signals and calculated values possible over a maximum of 32 points.
Galvanic isolation
Towards all other circuits