RMA42
Technical data
Hauser
45
Analog output:
10.0.5
Installation
Installation instructions
Mounting location
Mounting on top-hat rail as per IEC 60715.
Orientation
Vertical.
Environment
Ambient temperature range
-20 to +50 °C (-4 to 122 °F)
To avoid heat accumulation, always make sure the device is sufficiently cooled.
If the device is operated in the upper temperature limit range, this reduces the operating life of the
display.
Storage temperature
-40 to +85 °C (-40 to 185 °F)
Operating height
< 2000 m above MSL (6561 ft)
Climate class
As per IEC 60654-1, Class B2
Degree of protection
Top-hat rail housing IP 20
Condensation
Not permitted
AD converter resolution
16 bit
Temperature drift
Temperature drift:
≤
0.01%/ K (0.1%/18 °F) oMR
≤
0.02%/ K (0.2%/18 °F) oMR for Cu100, Cu50, Cu53, Pt50 and Pt46
Current
0/4 to 20 mA, overrange to
22 mA
± 0.05% of measuring range
Max. load
500
Ω
Max. inductance
10 mH
Max. capacitance
10
μ
F
Max. ripple
10 mVpp at 500
Ω
, frequency < 50 kHz
Voltage
0 to 10 V, 2 to 10 V
0 to 5 V
Overrange: up to 11 V, short-
circuit proof, I
max
< 25 mA
± 0.05% of measuring range
± 0.1% of measuring range
Max. ripple
10 mVpp at 1000
Ω
, frequency < 50 kHz
Resolution
13 bit
Temperature drift
0.01%/K (0.1%/18 °F) of of measuring range
Galvanic isolation
Testing voltage of 500 V towards all other circuits