Commissioning
RMA42
26
Hauser
Operating modes
Off
No action is triggered. The output assigned is always in the normal operating mode.
Min (lower limit value)
The limit value is active if the value configured is undershot. The limit value is switched off again if
the limit value incl. hysteresis is overshot.
a0010186-en
Fig. 9:
Min operating mode
Max (upper limit value)
The limit value is active if the value configured is overshot. The limit value is switched off again if
the limit value incl. hysteresis is undershot.
a0010187-en
Fig. 10:
Max operating mode