Commissioning
Prosonic S FMU95
60
E Hauser
•
horizontal cylinder
4)
•
sphere
In these linearization types the measured level is convertet to the volume in a horizontal cylinder
or a spherical tank.
The following additional parameters have to be specified:
– the unit of the linearized value, e.g. kg, m
3
, ft
3
, ... (
"customer unit"
)
– the diameter (D) of the tank (
"diameter"
)
– the maximum capacity (a) of the tank, measured in the customer unit (
"maximum scale"
).
•
angled bottom (A)
•
pyramid bottom (B)
•
conical bottom (B)
In these linearisation modes the measured level is converted to the volume in the respective type
of vessel.
The following additional parameters have to be specified:
– the unit for the linearized value, e.g. kg, m
3
, ft
3
, ... (
"customer unit"
)
– the intermediate height H according to the diagram (
"intermediate height"
)
– the maximum capacity (a) of the tank, measured in the customer unit (
"maximum scale"
).
4)
This option is only valid for horizontal cylinders without bumped ends. For tanks with bumped ends, a linearization table can be calculated and stored in the
instrument with the FieldCare operating program.
100%
20
mA
0%
0/4
mA
(D)Ø
(a)
kg
m
ft
3
3
100%
20
mA
0%
0/4
mA
= kg,m3, ft3, ...
H
(a)
A
B