Prosonic S FMU95
Commissioning
E Hauser
61
•
table
In this linearization mode the measured value is calculated from a linearization table. The table
may consist of up to 32 pairs of values (level - volume). The table must be monotonically
increasing or decreasing.
The following additional parameters have to be specified:
– the unit of the linearized value, e.g. kg, m
3
, ft
3
, ... (
"customer unit"
)
– the linearization table (
"edit"
)
100%
20
mA
0%
0/4
mA
kg
m
ft
3
3