4.5
Shortening the sensor cable
If required, the sensor cable can be shortened. Please note:
• Do not damage the cores when removing the insulation.
• The cable is shielded by a metallic braiding. This shielding serves as a return cable and
corresponds to the black (BK) strand of the unshortened cable. After shortening the cable, loosen
the metallic braiding, twist it together securely and connect it to the "BK" terminal.
"
Caution!
The protective earth conductor (GNYE), which is present in some of the sensor cables, may not be
electrically connected to the cable shield.