Technical Data
Prosonic S FMU95
92
E Hauser
10
Technical Data
10.1
Technical data at a glance
10.1.1
Input
Sensor inputs
Depending on the instrument version, up to 5 or up to 10 of the sensors FDU90, FDU91, FDU91F,
FDU92, FDU93, FDU95 and FDU96 can be connected. The Prosonic S identifies these sensors
automatically.
In order to support existing installations, the sensors of the former series FDU8x can be connected
as well. The type of sensor must be entered manually.
#
Warning!
The sensors FDU83, FDU84, FDU85 and FDU86 with an ATEX, FM or CSA certificate are not
certified for connection to the transmitter FMU95.
Sensor
FDU90
FDU91
FDU91F
FDU92
FDU93
FDU95
FDU96
max. range
1)
in liquids
1)
This table gives the maximum range. The range depends on the measuring conditions. For an estimation see
Technical Information TI00396F, chapter "Input".
3 (9.8)
10 (33)
20 (66)
25 (82)
-
-
max. range
1
in solids
1.2 (3.9)
5 (16)
10 (33)
15 (49)
45 (148)
70 (230)
m (ft)
Sensor
FDU80
FDU80F
FDU81
FDU81F
FDU82
FDU83
FDU84
FDU85
FDU86
max. range
1)
in liquids
1)
This table gives the maximum range. The range depends on the measuring conditions. For an estimation see
Technical Information TI00189F, chapter "Planning Recommendations".
5 (16)
10 (33)
20 (66)
25 (82)
-
-
-
max. range
1
in solids
2 (6.6)
5 (16)
10 (33)
15 (49)
25 (82)
45 (148)
70 (230)
m (ft)