Commissioning
Prosonic S FMU95
58
E Hauser
"LVL N unit" (N = 1 to 10)
"unit level"
Use this parameter to select the distance unit.
If no linearization is performed, the level is displayed in this unit.
Selection:
• m
• ft
• inch
• mm
•
% (Default)
"level N" (N = 1 - 10)
Displays the currently measured level F (from the zero point to the product surface) in the selected
unit.
L00-FMU90xxx-19-00-00-yy-021
"sensor"
Displays the currently measured distance D (from the sensor membrane (reference point of the
measurement) to the product surface) in the distance unit. If the display value does not match the
real distance, an interference echo suppression must be performed prior to linearization.
L00-FMU90xxx-19-00-00-yy-022
!
Note!
The distance unit is defined during the first setup of the instrument. If required, it can be changed
in the "device properties/operating params" menu.
LVL 1 unit level
L1007
unit level:
level 1:
sensor:
0/4 mA
0%
F
D