Operating Instructions

Proline Promass O 100

HART

Coriolis flowmeter

BA01191D/06/EN/01.14

71209780
Valid as of version

(Device firmware)

Summary of Contents for Proline Promass O 100HART

Page 1: ...Products Solutions Services Operating Instructions Proline Promass O 100 HART Coriolis flowmeter BA01191D 06 EN 01 14 71209780 Valid as of version Device firmware ...

Page 2: ...ger to individuals or the facility read the Basic safety instructions section carefully as well as all other safety instructions in the document that are specific to working procedures The manufacturer reserves the right to modify technical data without prior notice Your Endress Hauser Sales Center will supply you with current information and updates to these Instructions ...

Page 3: ... 6 2 3 Mounting the measuring device 24 6 3 Post installation check 24 7 Electrical connection 26 7 1 Connection conditions 26 7 1 1 Required tools 26 7 1 2 Requirements for connecting cable 26 7 1 3 Terminal assignment 27 7 1 4 Pin assignment device plug 28 7 1 5 Preparing the measuring device 28 7 2 Connecting the measuring device 28 7 2 1 Connecting the transmitter 28 7 3 Special connection ins...

Page 4: ... 1 Diagnostic options 79 12 3 2 Calling up remedy information 80 12 4 Adapting the diagnostic information 81 12 4 1 Adapting the diagnostic behavior 81 12 4 2 Adapting the status signal 81 12 5 Overview of diagnostic information 81 12 6 Pending diagnostic events 84 12 7 Diagnostic list 85 12 8 Event logbook 85 12 8 1 Event history 85 12 8 2 Filtering the event logbook 86 12 8 3 Overview of informa...

Page 5: ...n result in minor or medium injury NOTICE NOTE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Symbol Meaning Direct current A terminal to which DC voltage is applied or through which direct current flows Alternating current A terminal to which alternating voltage is applied or through which alternating current flows Di...

Page 6: ...are forbidden Tip Indicates additional information Reference to documentation Refers to the corresponding device documentation Reference to page Refers to the corresponding page number Reference to graphic Refers to the corresponding graphic number and page number Series of steps Result of a sequence of actions Help in the event of a problem Visual inspection 1 2 5 Symbols in graphics Symbol Meani...

Page 7: ...s all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device Brief Operating Instructions Guide that takes you quickly to the 1st measured value The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning 1 3 2 Supplementary device dependent documentation Additio...

Page 8: ...is an increased risk due to process pressure are labeled accordingly on the nameplate To ensure that the measuring device remains in proper condition for the operation time Only use the measuring device in full compliance with the data on the nameplate and the general conditions listed in the Operating Instructions and supplementary documentation Based on the nameplate check whether the ordered de...

Page 9: ...ional regulations For welding work on the piping Do not ground the welding unit via the measuring device If working on and with the device with wet hands It is recommended to wear gloves on account of the higher risk of electric shock 2 4 Operational safety Risk of injury Operate the device in proper technical condition and fail safe condition only The operator is responsible for interference free...

Page 10: ... described in the Operating Instructions The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings IT security measures in line with operators security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves ...

Page 11: ...HART communication type 3 2 1 4 5 6 7 A0023153 1 Important components of a measuring device 1 Sensor 2 Transmitter housing 3 Main electronics module 4 Transmitter housing cover 5 Transmitter housing cover version for optional onsite display 6 Onsite display optional 7 Main electronics module with bracket for optional onsite display ...

Page 12: ...ROM might not be part of the delivery In such cases the technical documentation is available via the Internet or via the Endress Hauser Operations App see the Product identification section 13 4 2 Product identification The following options are available for identification of the measuring device Nameplate specifications Order code with breakdown of the device features on the delivery note Enter ...

Page 13: ...ter the serial number from the nameplate or scan the 2 D matrix code QR code on the nameplate 4 2 1 Transmitter nameplate i 1 2 3 4 5 6 7 8 9 10 11 12 Order code Ext ord cd Ser no 13 A0017520 2 Example of a transmitter nameplate 1 Manufacturing location 2 Name of the transmitter 3 Order code 4 Serial number 5 Extended order code 6 Electrical connection data e g available inputs and outputs supply ...

Page 14: ...range 12 Degree of protection 13 Approval information for explosion protection and Pressure Equipment Directive 14 Permitted ambient temperature Ta 15 Document number of safety related supplementary documentation 112 16 CE mark C Tick 17 Flow direction 18 Manufacturing date year month 19 2 D matrix code Order code The measuring device is reordered using the order code Extended order code The devic...

Page 15: ...ng WARNING This symbol alerts you to a dangerous situation Failure to avoid this situation can result in serious or fatal injury A0011194 Reference to documentation Refers to the corresponding device documentation A0011199 Protective ground connection A terminal which must be connected to ground prior to establishing any other connections ...

Page 16: ...e webbing slings Risk of injury if the measuring device slips Secure the measuring device from rotating or slipping Observe the weight specified on the packaging stick on label Observe the transport instructions on the stick on label on the electronics compartment cover A0015606 Observe the following notes during transport Transport the measuring device to the measuring point in the original packa...

Page 17: ...kaging Wood crate treated in accordance with ISPM 15 standard which is confirmed by the affixed IPPC logo or Carton in accordance with European Packaging Directive 94 62EC recyclability is confirmed by the affixed RESY symbol Seaworthy packaging optional Wood crate treated in accordance with ISPM 15 standard which is confirmed by the affixed IPPC logo Carrying and mounting hardware Disposable plas...

Page 18: ...ounting locations in the pipe Highest point of a pipeline Directly upstream of a free pipe outlet in a down pipe A0023344 Installation in down pipes However the following installation suggestion allows for installation in an open vertical pipeline Pipe restrictions or the use of an orifice with a smaller cross section than the nominal diameter prevent the sensor running empty while measurement is ...

Page 19: ...ad at side A0015592 1 Applications with low process temperatures may reduce the ambient temperature To maintain the minimum ambient temperature for the transmitter this orientation is recommended 2 Applications with high process temperatures may increase the ambient temperature To maintain the maximum ambient temperature for the transmitter this orientation is recommended If a sensor is installed ...

Page 20: ...50 to 60 C 58 to 140 F Order code for Test certificate option JM Local display 20 to 60 C 4 to 140 F The readability of the display may be impaired at temperatures outside the temperature range If operating outdoors Avoid direct sunlight particularly in warm climatic regions System pressure It is important that cavitation does not occur or that gases entrained in the liquids do not outgas Cavitati...

Page 21: ...ely exposed 0 20 60 40 80 in 1 2 3 0 t 100 4 mm T40 104 T60 140 80 100 120 140 200 300 400 160 180 200 F Tm C A0023177 6 Recommended insulation thicknesses depending on the medium and ambient temperature t Insulation thickness Tm Medium temperature T40 104 Insulation thickness with ambient temperature of Ta 40 C 104 F T60 140 Insulation thickness with ambient temperature of Ta 60 C 140 F NOTICE Th...

Page 22: ...re greater than the values approved by the EN standard sine 30 A m For this reason the sensor must be magnetically shielded the housing can be shielded with tin plates or electric sheets without a privileged direction e g V330 35A The sheet must have the following properties Relative magnetic permeability µr 300 Plate thickness d 0 35 mm d 0 014 in Vibrations The high oscillation frequency of the ...

Page 23: ...disk do not use a heating jacket Make sure that the function and operation of the rupture disk is not impeded through the installation of the device Take precautions to prevent damage and danger to persons if the rupture disk is actuated Observe information on the rupture disk sticker Zero point adjustment All measuring devices are calibrated in accordance with state of the art technology Calibrat...

Page 24: ...t the direction of the arrow on the nameplate of the sensor matches the flow direction of the fluid 2 Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards A0013964 6 3 Post installation check Is the device undamaged visual inspection Does the measuring device conform to the measuring point specifications For example Process temperature 104 Pro...

Page 25: ...Proline Promass O 100 HART Installation Endress Hauser 25 Is the device adequately protected from precipitation and direct sunlight Are the securing screw and securing clamp tightened securely ...

Page 26: ...d cables crimping tool for ferrule 7 1 2 Requirements for connecting cable The connecting cables provided by the customer must fulfill the following requirements Electrical safety In accordance with applicable federal national regulations Permitted temperature range 40 C 40 F to 80 C 176 F Minimum requirement cable temperature range ambient temperature 20 K Power supply cable Standard installation...

Page 27: ...nals Option L plug M12x1 thread NPT Option N plug M12x1 coupling M20 Option P plug M12x1 thread G Option U plug M12x1 thread M20 Options A B C Device plug Device plug Option Q 2 x plug M12x1 Order code for Housing Option A compact coated aluminum Option B compact stainless Option B compact stainless M12 device plug L L 26 27 _ 24 25 1 2 _ _ 1 2 3 A0016888 7 Terminal assignment 4 20 mA HART with pu...

Page 28: ...g device could be compromised Use suitable cable glands corresponding to the degree of protection If measuring device is delivered without cable glands Provide suitable cable gland for corresponding connecting cable 26 3 If measuring device is delivered with cable glands Observe cable specification 26 7 2 Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect conne...

Page 29: ...plug for supply voltage C Housing version ultra compact hygienic stainless M12 device plug 3 Device plug for signal transmission 4 Device plug for supply voltage 10 0 4 mm in 1 2 3 2 1 2 1 2 3 8 mm 3 mm 8 mm A0017844 9 Device versions with connection examples 1 Cable 2 Device plug for signal transmission 3 Device plug for supply voltage For device version with device plug only pay attention to Ste...

Page 30: ...verse the removal procedure to reassemble the transmitter 7 3 Special connection instructions 7 3 1 Connection examples 7 4 Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66 67 degree of protection Type 4X enclosure To guarantee IP66 67 degree of protection Type 4X enclosure carry out the following steps after the electrical connection 1 Check that t...

Page 31: ...oes the supply voltage match the specifications on the transmitter nameplate 99 Is the terminal assignment or the pin assignment of the device plug correct If supply voltage is present is the power LED on the electronics module of the transmitter lit green 11 Depending on the device version is the securing clamp or fixing screw firmly tightened ...

Page 32: ...Operation options 8 1 Overview of operation options 1 2 3 4 A0019598 1 Computer with Web browser e g Internet Explorer or with operating tool e g FieldCare AMS Device Manager SIMATIC PDM 2 Field Xpert SFX350 or SFX370 3 Field Communicator 475 4 Control system e g PLC ...

Page 33: ... display Output Operating menu for experts Language Operatation Language Parameter 1 Setup Submenu 1 Submenu n Device tag Advanced setup Enter access code Parameter 1 Parameter n Submenu 1 Submenu n Diagnostics Parameter 1 Parameter n Submenu 1 Submenu n Operating menu for operators and maintenances Parameter n Operator Maintenance Task orie nted Function oriented Expert Wizard 1 Parameter 1 Wizar...

Page 34: ...s Data logging submenu order option Extended HistoROM Storage and visualization of up to 1000 measured values Heartbeat Technology submenu The functionality of the device is checked on demand and the verification results are documented Simulation submenu Is used to simulate measured values or output values Expert function oriented Tasks that require detailed knowledge of the function of the device...

Page 35: ...ware version To enable correct data display clear the temporary memory cache of the Web browser under Internet options 8 3 3 Establishing a connection Configuring the Internet protocol of the computer The following information refers to the default Ethernet settings of the device IP address of the device 192 168 1 212 factory setting IP address 192 168 1 XXX for XXX all numerical values except 0 2...

Page 36: ... Logging on 1 Select the preferred operating language for the Web browser 2 Enter the access code 3 Press OK to confirm your entry Access code 0000 factory setting can be changed by customer 72 If no action is performed for 10 minutes the Web browser automatically returns to the login page 8 3 5 User interface 2 4 6 5 1 3 2 4 6 5 1 3 2 4 6 5 1 3 2 4 6 5 1 3 2 4 6 5 1 3 A0017757 EN 1 2 3 4 5 6 Pict...

Page 37: ...ith the Heartbeat Verification application package Network configuration Configuration and checking of all the parameters required for establishing the connection to the device Network settings e g IP address MAC address Device information e g serial number firmware version Logout End the operation and call up the login page Navigation area If a function is selected in the function bar the submenu...

Page 38: ...se the Web browser 3 Reset the modified properties of the Internet protocol TCP IP if they are no longer needed 35 8 4 Access to the operating menu via the operating tool 8 4 1 Connecting the operating tool Via HART protocol This communication interface is present in the following device version Order code for Output option B 4 20 mA HART pulse frequency switch output 1 2 3 5 7 4 6 A0016948 11 Opt...

Page 39: ...enable efficient device configuration and diagnostics for HART and FOUNDATION fieldbus devices in the non Ex area SFX350 SFX370 and the Ex area SFX370 For details see Operating Instructions BA01202S Source for device description files See data 43 8 4 3 FieldCare Function scope FDT based plant asset management tool from Endress Hauser It can configure all smart field devices in a system and helps y...

Page 40: ...n from the list and press OK to confirm 4 Right click CDI Communication TCP IP and select the Add device option in the context menu that opens 5 Select the desired device from the list and press OK to confirm The CDI Communication TCP IP Configuration window opens 6 Enter the device address in the IP address field and press Enter to confirm 192 168 1 212 factory setting if the IP address is not kn...

Page 41: ... with status signal 80 6 Display area for current measured values 74 7 Event list with additional functions such as save load events list and document creation 8 Navigation area with operating menu structure 9 Operating range 10 Range of action 11 Status area 8 4 4 AMS Device Manager Function scope Program from Emerson Process Management for operating and configuring measuring devices via HART pro...

Page 42: ...RT 42 Endress Hauser 8 4 6 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol Source for device description files See data 43 ...

Page 43: ... individual operating tools is listed in the table below along with information on where the file can be acquired Operating tool via HART protocol Sources for obtaining device descriptions Field Xpert SFX350 Field Xpert SFX370 Use update function of handheld terminal FieldCare www endress com Download Area CD ROM contact Endress Hauser DVD contact Endress Hauser AMS Device Manager Emerson Process ...

Page 44: ...ry tertiary and quaternary dynamic variable Mass flow Volume flow Corrected volume flow Density Reference density Temperature Totalizer 1 Totalizer 2 Totalizer 3 The range of options increases if the measuring device has one or more application packages Heartbeat Technology Application Package Additional measured variables are available with the Heartbeat Technology application package Carrier pip...

Page 45: ...tory setting Burst mode Activation of the HART burst mode for burst message X An external pressure or temperature sensor must also be in the Burst mode Off On Off Burst command Select the HART command that is sent to the HART master Command 1 option Read out the primary variable Command 2 option Read out the current and the main measured value as a percentage Command 3 option Read out the dynamic ...

Page 46: ... 0 Not used Burst variable 5 See burst variable 0 See burst variable 0 Not used Burst variable 6 See burst variable 0 See burst variable 0 Not used Burst variable 7 See burst variable 0 See burst variable 0 Not used Burst trigger mode Use this function to select the event that triggers burst message X Continuous option The message is triggered in a time controlled manner at least observing the tim...

Page 47: ...er entry Factory setting Min update period Use this function to enter the minimum time span between two burst commands of burst message X Positive integer 1000 ms Max update period Use this function to enter the maximum time span between two burst commands of burst message X Positive integer 2000 ms ...

Page 48: ...ff 63 Partially filled pipe detection 64 HART input 59 Advanced setup 65 10 2 1 Defining the tag name To enable fast identification of the measuring point within the system you can enter a unique designation using the Device tag parameter and thus change the factory setting The number of characters displayed depends on the characters used For information on the tag name in the FieldCare operating ...

Page 49: ...tion process variable Unit choose list Country specific kg h lb min Mass unit Select mass unit Result The selected unit is taken from Mass flow unit parameter Unit choose list Country specific kg lb Volume flow unit Select volume flow unit Result The selected unit applies for Output Low flow cut off Simulation process variable Unit choose list Country specific l h gal min us Volume unit Select vol...

Page 50: ...it Result The selected unit applies for Output Simulation process variable Density adjustment in Expert menu Unit choose list Country specific kg l lb ft Reference density unit Select reference density unit Unit choose list kg Nl Temperature unit Select temperature unit Result The selected unit applies for Output Reference temperature Simulation process variable Unit choose list Country specific C...

Page 51: ... type choose list Methane CH4 Reference sound velocity The following option is selected in the Select gas type parameter Others Enter sound velocity of gas at 0 C 32 F 1 to 99999 9999 m s 0 m s Temperature coefficient sound velocity The following option is selected in the Select gas type parameter Others Enter temperature coefficient for the gas sound velocity Positive floating point number 0 m s ...

Page 52: ...e Current output 2 submenu contains all the parameters that must be configured for the configuration of the current output Navigation Setup menu Current output 1 to 2 Structure of the submenu Current output 1 to 2 Assign current output Current span 4 mA value 20 mA value Failure mode Failure current ...

Page 53: ...g fluctuation 1 Signal asymmetry Exciter current 0 Exciter current 1 Sensor integrity Mass flow Mass flow unit Select mass flow unit Result The selected unit applies for Output Low flow cut off Simulation process variable Unit choose list Country specific kg h lb min Volume flow unit Select volume flow unit Result The selected unit applies for Output Low flow cut off Simulation process variable Un...

Page 54: ...ncy or switch output Pulse Frequency Switch Pulse Assign pulse output Select process variable for pulse output Off Mass flow Volume flow Corrected volume flow Target mass flow Carrier mass flow Off Mass unit Select mass unit Result The selected unit is taken from Mass flow unit parameter Unit choose list Country specific kg lb Volume unit Select volume unit Result The selected unit is taken from V...

Page 55: ... or switch output Pulse Frequency Switch Pulse Assign frequency output Select process variable for frequency output Off Mass flow Volume flow Corrected volume flow Target mass flow Carrier mass flow Density Reference density Concentration Dynamic viscosity Kinematic viscosity Temp compensated dynamic viscosity Temp compensated kinematic viscosity Temperature Carrier pipe temperature Electronic tem...

Page 56: ...0 Hz 10000 0 Hz Measuring value at minimum frequency Enter measured value for minmum frequency Signed floating point number 0 Measuring value at maximum frequency Enter measured value for maximum frequency Signed floating point number 0 Failure mode Define output behavior in alarm condition Actual value Defined value 0 Hz 0 Hz Failure frequency Enter frequency output value in alarm condition 0 0 t...

Page 57: ...izer 3 Measuring tube damping Mass flow Assign flow direction check Select process variable for flow direction monitoring Off Volume flow Mass flow Corrected volume flow Mass flow Assign status Select device status for switch output Partially filled pipe detection Low flow cut off Partially filled pipe detection Mass flow unit Select mass flow unit Result The selected unit applies for Output Low f...

Page 58: ...Invert output signal Invert the output signal No Yes No 10 2 6 Configuring the local display The Display wizard guides you systematically through all the parameters that can configured for configuring the local display Navigation Setup menu Display Structure of the wizard Format display Value 1 display 0 bargraph value 1 100 bargraph value 1 Value 2 display Value 3 display 0 bargraph value 3 100 b...

Page 59: ...lation damping 1 Tube damping fluctuation 0 Tube damping fluctuation 1 Signal asymmetry Exciter current 0 Exciter current 1 Sensor integrity None Totalizer 1 Totalizer 2 Totalizer 3 Current output 1 Mass flow 0 bargraph value 1 Enter 0 value for bar graph display Signed floating point number 0 kg h 100 bargraph value 1 Enter 100 value for bar graph display Signed floating point number 2 5 kg h Val...

Page 60: ...vice 0 to 255 0 Burst command Select command to read in external process variable Command 1 Command 3 Command 9 Command 33 Command 1 Slot number Define position of external process variable in burst command 1 to 4 1 Timeout Enter deadline for process variable of external device If the deadline is exceeded diagnostic message F410 data transmission is output 1 to 120 s 5 s Failure mode Define behavi...

Page 61: ...Density Reference density Concentration Dynamic viscosity Kinematic viscosity Temp compensated dynamic viscosity Temp compensated kinematic viscosity Temperature Carrier pipe temperature Electronic temperature Oscillation frequency 0 Oscillation frequency 1 Oscillation amplitude 0 Oscillation amplitude 1 Frequency fluctuation 0 Frequency fluctuation 1 Oscillation damping 0 Oscillation damping 1 Tu...

Page 62: ...e 1 Oscillation damping 0 Oscillation damping 1 Tube damping fluctuation 0 Tube damping fluctuation 1 Signal asymmetry Exciter current 0 Exciter current 1 Off Damping output Set reaction time for output signal to fluctuations in the measured value 0 to 999 9 s 1 s Measuring mode output Select measuring mode for output Forward flow Forward Reverse flow Reverse flow Reverse flow compensation Forward...

Page 63: ... flow Volume flow Corrected volume flow Mass flow On value low flow cutoff One of the following options is selected in the Assign process variable parameter Mass flow Volume flow Corrected volume flow Enter on value for low flow cut off Positive floating point number For liquids depends on country and nominal diameter Off value low flow cutoff One of the following options is selected in the Assign...

Page 64: ...ion Off Density Reference density Off Low value partial filled pipe detection One of the following options is selected in the Assign process variable parameter Density Reference density Enter lower limit value for deactivating partialy filled pipe detection Signed floating point number Country dependent 0 2 kg l 12 5 lb ft High value partial filled pipe detection One of the following options is se...

Page 65: ...setup Define access code 36 Define access code 72 Calculated values 65 Sensor adjustment 66 Totalizer1 to 3 67 10 3 1 Calculated values The Calculated values submenu contains parameters for calculating the corrected volume flow Navigation Setup menu Advanced setup Calculated values Structure of the submenu Calculated values Corrected volume flow calculation Corrected volume flow calculation Extern...

Page 66: ...in the Corrected volume flow calculation parameter Calculated reference density Enter reference temperature for calculating the reference density 273 15 to 99999 C 20 C Linear expansion coefficient The following option is selected in the Corrected volume flow calculation parameter Calculated reference density Enter linear medium specific expansion coefficient for calculating the reference density ...

Page 67: ... the Totalizer 1 to 3 submenu the individual totalizers can be configured Navigation Setup menu Advanced setup Totalizer 1 to 3 Totalizer 1 to 3 Assign process variable Unit totalizer Failure mode Parameter overview with brief description Parameter Description Selection Factory setting Assign process variable Select process variable for totalizer Off Volume flow Mass flow Corrected volume flow Tar...

Page 68: ...ocal display Navigation Setup menu Advanced setup Display Structure of the submenu Display Format display Value 1 display 0 bargraph value 1 100 bargraph value 1 Decimal places 1 Value 2 display Decimal places 2 Value 3 display 0 bargraph value 3 100 bargraph value 3 Decimal places 3 Value 4 display Decimal places 4 Display language Display interval Display damping Header Header text Separator Bac...

Page 69: ...Oscillation damping 0 Oscillation damping 1 Tube damping fluctuation 0 Tube damping fluctuation 1 Signal asymmetry Exciter current 0 Exciter current 1 Sensor integrity None Totalizer 1 Totalizer 2 Totalizer 3 Current output 1 Mass flow 0 bargraph value 1 Enter 0 value for bar graph display Signed floating point number 0 kg h 100 bargraph value 1 Enter 100 value for bar graph display Signed floatin...

Page 70: ...glish alternatively the ordered language is preset in the device Display interval Set time measured values are shown on display if display alternates between values 1 to 10 s 5 s Display damping Set display reaction time to fluctuations in the measured value 0 0 to 999 9 s 0 0 s Header Select header contents on local display Device tag Free text Device tag Header text Enter display header text Sep...

Page 71: ...le is selected in the Assign simulation process variable parameter Enter the simulation value for the selected process variable Signed floating point number 0 Simulation current output 1 Switch simulation of the current output on and off Off On Off Value current output 1 The On option is selected in the Current output simulation parameter Enter the current value for simulation 3 59 3 to 22 5 3 mA ...

Page 72: ...access The following options exist for protecting the configuration of the measuring device from unintentional modification after commissioning Write protection via access code for Web browser 72 Write protection via write protection switch 73 10 5 1 Write protection via access code With the customer specific access code access to the measuring device via the Web browser is protected as are the pa...

Page 73: ...ring clamp or fixing screw of the housing cover 2 Depending on the housing version unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary 108 3 Disconnect the T DAT from the main electronics module 4 Setting the write protection switch on the main electronics module to the ON position enables the hardware write protection Setting the wri...

Page 74: ...oading of data reset write access to the parameters is blocked for a short time Once the internal processing has been completed the parameters can be changed once again 11 2 Configuring the display Basic settings for local display 58 Advanced settings for local display 68 11 3 Reading measured values Using the Measured values submenu it is possible to read all the measured values Diagnostics menu ...

Page 75: ...ns all the parameters needed to display the current measured values for every totalizer Navigation Diagnostics menu Measured values Totalizer Structure of the submenu Totalizer Totalizer value Totalizer overflow Parameter overview with brief description Parameter Prerequsite Description User interface Factory setting Totalizer value 1 In the Assign process variable parameter of Totalizer 1 to 3 su...

Page 76: ...s 1 Displays the current switch output status Open Closed Open 11 4 Adapting the measuring device to the process conditions The following are available for this purpose Basic settings using the Setup menu 48 Advanced settings using the Advanced setup submenu 65 11 5 Performing a totalizer reset In the Operation submenu the totalizers are reset Control Totalizer Reset all totalizers Function scope ...

Page 77: ...u Operation Structure of the submenu Operation Control Totalizer Preset value Reset all totalizers Parameter overview with brief description Parameter Description Selection User entry Factory setting Control Totalizer Control totalizer value Totalize Reset hold Preset hold Reset totalize Preset totalize Totalize Preset value Specify start value for totalizer Signed floating point number 0 kg Reset...

Page 78: ...rrectly Observe the documentation for the Commubox FXA195 HART Document Technical Information TI00404F Not connecting to Web server Incorrect setting for the Ethernet interface of the computer 1 Check the properties of the Internet protocol TCP IP 35 2 Check the network settings with the IT manager Not connecting to Web server Web server disabled Via the FieldCare operating tool check whether the ...

Page 79: ...detected by the measuring device are displayed on the home page of the operating tool once the connection has been established Xxxxxx Xxxxxx P P P Diagnostics 1 Remedy information Failure F Function check C Out of spezification S Maintenance required M C485 Simulation measured vari Deactivate Simulation Service Diagnostics 1 C485 Simu Remedy information Deactivate Access status tooling Mainenance ...

Page 80: ...ill valid The status signals are categorized in accordance with VDI VDE 2650 and NAMUR Recommendation NE 107 Diagnostic information The fault can be identified using the diagnostic information The short text helps you by providing information about the fault Diagnostic information Diagnostic code Status signal Diagnostic number Short text Example A0013958 842 Process limit 3 digit number 12 3 2 Ca...

Page 81: ... ignored and no diagnostic message is generated or entered 12 4 2 Adapting the status signal Each item of diagnostic information is assigned a specific status signal at the factory The user can change this assignment for certain diagnostic information in the Diagnostic event category submenu Expert menu Communication Diagnostic event category Available status signals Configuration as per HART 7 Sp...

Page 82: ...ervice F Alarm 192 Special event 9 Contact service F Alarm 1 Diagnostic of electronic 201 Device failure 1 Restart device 2 Contact service F Alarm 242 Software incompatible 1 Check software 2 Flash or change main electronics module F Alarm 252 Modules incompatible 1 Check electronic modules 2 Change electronic modules F Alarm 262 Module connection 1 Check module connections 2 Change main electron...

Page 83: ... 1 442 Frequency output 1 Check process 2 Check frequency output settings S Warning 1 443 Pulse output 1 Check process 2 Check pulse output settings S Warning 1 453 Flow override Deactivate flow override C Warning 484 Simulation failure mode Deactivate simulation C Alarm 485 Simulation measured variable Deactivate simulation C Warning 491 Simulation current output 1 Deactivate simulation C Warning...

Page 84: ...n 2 Check external device or process conditions F Alarm 910 Tubes not oscillating 1 Check electronic 2 Inspect sensor F Alarm 912 Medium inhomogeneous 1 Check process cond 2 Increase system pressure S Warning 912 Inhomogeneous 1 Check process cond 2 Increase system pressure S Warning 913 Medium unsuitable 1 Check process conditions 2 Check electronic modules or sensor S Alarm 944 Monitoring failed...

Page 85: ...agnostic code and short message 12 7 Diagnostic list In the Diagnostic list submenu up to 5 currently pending diagnostic events can be displayed along with the related diagnostic information If more than 5 diagnostic events are pending the events with the highest priority are shown on the display Navigation path Diagnostics menu Diagnostic list submenu To call up the measures to rectify a diagnost...

Page 86: ...nts Unlike a diagnostic event an information event is displayed in the event logbook only and not in the diagnostic list Info number Info name I1000 Device ok I1089 Power on I1090 Configuration reset I1091 Configuration changed I1110 Write protection switch changed I1111 Density adjust failure I1137 Electronic changed I1151 History reset I1155 Reset electronic temperature I1157 Memory error event ...

Page 87: ...of the configuration to a defined state Setup menu Advanced setup Administration Function scope of Device reset parameter Options Description Cancel No action is executed and the user exits the parameter To delivery settings Every parameter for which a customer specific default setting was ordered is reset to this customer specific value All other parameters are reset to the factory setting This o...

Page 88: ...he following format xx yy zz 01 01 Device name Displays the name of the transmitter Character string composed of letters numbers and certain punctuation marks Promass 100 Order code Displays the device order code Character string composed of letters numbers and certain punctuation marks Extended order code 1 Displays the 1st part of the extended order code Character string Extended order code 2 Di...

Page 89: ...tation type Documentation 04 2013 01 00 00 Option 76 Original firmware Operating Instructions 06 2014 01 01 zz Option 70 In accordance with HART 7 Specification Integration of optional onsite display New unit Beer Barrel BBL Monitoring of measuring tube damping Simulation of diagnostic events External verification of the current and PFS output via the Heartbeat application package Fixed value for ...

Page 90: ...bserve the maximum permitted medium temperature for the measuring device 104 13 2 Measuring and test equipment Endress Hauser offers a wide variety of measuring and test equipment such as W M or device tests Your Endress Hauser Sales Center can provide detailed information on the services For a list of some of the measuring and test equipment refer to the Accessories chapter of the Technical Infor...

Page 91: ...m into the W M life cycle management database 14 2 Spare parts Measuring device serial number Is located on the nameplate of the device Can be read out via the Serial number parameter in the Device information submenu 87 14 3 Endress Hauser services Contact your Endress Hauser Sales Center for information on services and spare parts 14 4 Return The measuring device must be returned if repairs or a...

Page 92: ...ing of the measuring device WARNING Danger to personnel and environment from fluids that are hazardous to health Ensure that the measuring device and all cavities are free of fluid residues that are hazardous to health or the environment e g substances that have permeated into crevices or diffused through plastic Observe the following notes during disposal Observe valid federal national regulation...

Page 93: ... mA measuring devices via a Web browser For details see Technical Information TI00025S and Operating Instructions BA00053S Fieldgate FXA520 Gateway for the remote diagnostics and remote configuration of connected HART measuring devices via a Web browser For details see Technical Information TI00025S and Operating Instructions BA00051S Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for ...

Page 94: ...t tool from Endress Hauser It can configure all smart field units in your system and helps you manage them By using the status information it is also a simple but effective way of checking their status and condition For details see Operating Instructions BA00027S and BA00059S 15 3 System components Accessories Description Memograph M graphic display recorder The Memograph M graphic display recorde...

Page 95: ...oriolis measuring principle Measuring system One device version is available compact version transmitter and sensor form a mechanical unit For information on the structure of the device 11 16 3 Input Measured variable Direct measured variables Mass flow Density Temperature Calculated measured variables Volume flow Corrected volume flow Reference density Measuring range Measuring ranges for liquids...

Page 96: ...section 105 Operable flow range Over 1000 1 Flow rates above the preset full scale value are not overridden by the electronics unit with the result that the totalizer values are registered correctly 16 4 Output Output signal Current output Current output 4 20 mA HART active Maximum output values DC 24 V no flow 22 5 mA Load 0 to 700 Ω Resolution 0 38 µA Damping Adjustable 0 07 to 999 s Assignable ...

Page 97: ...vice has one or more application packages Switch output Switching behavior Binary conductive or non conductive Switching delay Adjustable 0 to 100 s Number of switching cycles Unlimited Assignable functions Off On Diagnostic behavior Limit value Mass flow Volume flow Corrected volume flow Density Reference density Temperature Totalizer 1 3 Flow direction monitoring Status Partially filled pipe det...

Page 98: ...ight Red backlighting indicates a device error Status signal as per NAMUR recommendation NE 107 Operating tool Via digital communication HART protocol Via service interface Plain text display With information on cause and remedial measures Web browser Plain text display With information on cause and remedial measures Low flow cut off The switch points for low flow cut off are user selectable Galva...

Page 99: ...ter Order code for Output Maximum Current consumption Maximum switch on current Option B 4 20mA HART pul freq switch output 145 mA 18 A 0 125 ms Power supply failure Totalizers stop at the last value measured Depending on the device version the configuration is retained in the device memory or in the plug in memory HistoROM DAT Error messages incl total operated hours are stored Electrical connect...

Page 100: ...gn fundamentals 102 Density liquids Reference conditions 0 0005 g cm Standard density calibration 0 01 g cm valid over the entire temperature range and density range Wide range density specification order code for Application package option EF Special density and concentration 0 001 g cm valid range for special density calibration 0 to 2 g cm 5 to 80 C 41 to 176 F Temperature 0 5 C 0 005 T C 0 9 F...

Page 101: ...et IP Current output Accuracy Max 0 05 o f s or 5 µA Pulse frequency output Accuracy Max 50 ppm o r Repeatability o r of reading 1 g cm3 1 kg l T medium temperature Base repeatability Mass flow and volume flow liquids 0 025 o r PremiumCal for mass flow 0 05 o r Mass flow gases 0 25 o r Design fundamentals 102 Density liquids 0 00025 g cm3 Temperature 0 25 C 0 0025 T C 0 45 F 0 0015 T 32 F Response...

Page 102: ...al density calibration If the process temperature is outside the valid range 100 the measured error is 0 00005 g cm3 C 0 000025 g cm3 F kg m 3 C 40 0 80 40 80 120 160 200 240 280 320 360 400 F 40 0 50 100 150 200 0 2 4 6 8 10 2 1 A0016612 1 Field density calibration for example at 20 C 68 F 2 Special density calibration Temperature 0 005 T C 0 005 T 32 F Influence of medium pressure The table belo...

Page 103: ...m repeatability in o r ZeroPoint BaseRepeat 100 A0021335 A0021340 ZeroPoint BaseRepeat 100 A0021336 ZeroPoint MeasValue 100 A0021337 Example for max measured error E Q 0 5 10 15 20 25 30 35 40 45 50 60 65 55 0 0 5 1 0 1 5 2 0 2 5 70 75 80 85 90 95 100 A0016708 E Error Maximum measured error as o r example using PremiumCal Q Flow rate as Design fundamentals 102 16 7 Installation Mounting requiremen...

Page 104: ...or industry as per EN 55011 Class A For details refer to the Declaration of Conformity 16 9 Process Medium temperature range Sensor 40 to 200 C 40 to 392 F Seals No internal seals Density 0 to 5000 kg m3 0 to 312 lb cf Pressure temperature ratings An overview of the pressure temperature ratings for the process connections is provided in the Technical Information document Secondary containment pres...

Page 105: ...e device is fitted with a rupture disk the rupture disk is decisive for the maximum nominal pressure 105 For the dimensions and installation lengths of the device see the Technical Information document Mechanical construction section Rupture disk To increase the level of safety a device version with a rupture disk with a triggering pressure of 10 to 15 bar 145 to 217 5 psi can be used Special moun...

Page 106: ...fer to devices with Class 900 flanges Weight information in lbs DN in Weight lbs 3 161 4 306 6 538 Materials Transmitter housing Order code for Housing option A Compact aluminum coated Aluminum AlSi10Mg coated Order code for Housing option B Compact stainless Stainless steel 1 4404 316L Order code for Housing option C Ultra compact stainless Stainless steel 1 4404 316L Cable entries cable glands 1...

Page 107: ...ble gland M20 1 5 Stainless steel 1 4404 316L Adapter for cable entry with internal thread G Adapter for cable entry with internal thread NPT Device plug Electrical connection Material Plug M12x1 Socket Stainless steel 1 4404 316L Contact housing Polyamide Contacts Gold plated brass Sensor housing Acid and alkali resistant outer surface Stainless steel 1 4404 316L Measuring tubes Stainless steel 2...

Page 108: ...dule In the case of the Compact hygienic stainless and Ultra compact hygienic stainless housing versions the local display is integrated in the housing cover and is disconnected from the main electronics module when the housing cover is opened Compact aluminum coated housing version The local display is plugged onto the main electronics module The electronic connection between the local display an...

Page 109: ...r code for Output option B 4 20 mA HART pulse frequency switch output 1 Service interface CDI RJ45 of the measuring device with access to the integrated Web server 2 Computer with Web browser e g Internet Explorer for accessing the integrated device Web server or with FieldCare operating tool with COM DTM CDI Communication TCP IP 3 Standard Ethernet connecting cable with RJ45 plug Languages Can be...

Page 110: ... range of application is indicated in tables 6 to 9 in Annex II of the Pressure Equipment Directive Other standards and guidelines EN 60529 Degrees of protection provided by enclosures IP code IEC EN 60068 2 6 Environmental influences Test procedure Test Fc vibrate sinusoidal IEC EN 60068 2 31 Environmental influences Test procedure Test Ec shocks due to rough handling primarily for devices EN 610...

Page 111: ...ice functionality on demand when the device is installed without having to interrupt the process Access via onsite operation or other operating interfaces such as FieldCare for instance Documentation of device functionality within the framework of manufacturer specifications for proof testing for instance End to end traceable documentation of the verification results including report Makes it poss...

Page 112: ...ctions Measuring device Documentation code Promass O 100 KA01147D Technical Information Measuring device Documentation code Promass O 100 TI01107D Supplementary device dependent documentation Safety Instructions Contents Documentation code ATEX IECEx Ex i XA00159D ATEX IECEx Ex nA XA01029D cCSAus IS XA00160D INMETRO Ex i XA01219D INMETRO Ex nA XA01220D NEPSI Ex i XA01249D NEPSI Ex nA XA01262D Spec...

Page 113: ... of the parameter can be found in the manual 17 1 1 Main menu Main menu Operation 113 Setup 113 Diagnostics 118 Expert 121 17 1 2 Operation menu Operation Display language 70 Web server language Access status display Access status tooling Locking status 72 Display 58 Format display 59 Contrast display Backlight 70 Display interval 70 Totalizer handling 76 Control Totalizer 1 to 3 77 Preset value 1...

Page 114: ...rent output 1 52 Assign current output 53 Current span 53 4 mA value 53 20 mA value 53 Failure mode 53 Failure current 53 Pulse frequency switch output 54 Operating mode 54 Assign pulse output 54 Assign frequency output 55 Switch output function 57 Assign diagnostic behavior 57 Assign limit 57 Assign flow direction check 57 Assign status 57 Value per pulse 54 Pulse width 54 Failure mode 54 Minimum...

Page 115: ...utput 53 Damping output 1 61 Measuring mode output 1 61 Assign pulse output 54 Measuring mode output 1 62 Operating mode totalizer 1 3 62 Low flow cut off 63 Assign process variable 63 On value low flow cutoff 63 Off value low flow cutoff 63 Pressure shock suppression 63 Partially filled pipe detection 64 Assign process variable 64 Low value partial filled pipe detection 64 High value partial fill...

Page 116: ...s flow unit 49 Mass unit 49 Volume flow unit 49 Volume unit 49 Corrected volume flow unit 49 Corrected volume unit 50 Density unit 50 Reference density unit 50 Temperature unit 50 Pressure unit 50 Calculated values 65 Corrected volume flow calculation 65 Corrected volume flow calculation 66 External reference density 66 Fixed reference density 66 Reference temperature 66 Linear expansion coefficie...

Page 117: ... Totalizer operation mode 67 Failure mode 67 Display 68 Format display 59 Value 1 display 59 0 bargraph value 1 59 100 bargraph value 1 59 Decimal places 1 69 Value 2 display 59 Decimal places 2 69 Value 3 display 59 0 bargraph value 3 59 100 bargraph value 3 59 Decimal places 3 70 Value 4 display 59 Decimal places 4 70 Display language 70 Display interval 70 Display damping 70 Header 70 Header te...

Page 118: ...ccess code 72 Device reset 87 1 Order code for Application package option ED Concentration see the Special Documentation for the device 2 Order code for Application package option EB Heartbeat Verification and Monitoring see Special Documentation for the device 17 1 4 Diagnostics menu Diagnostics 118 78 Actual diagnostics 85 Previous diagnostics 85 Operating time from restart 85 Operating time 0 D...

Page 119: ...pe 89 Manufacturer ID 89 IP address 89 Subnet mask 89 Default gateway 89 Measured values 74 Process variables 74 Mass flow 75 Volume flow 75 Corrected volume flow 75 Density 75 Reference density 75 Temperature 75 Pressure value 75 Dynamic viscosity Kinematic viscosity Temp compensated dynamic viscosity Temp compensated kinematic viscosity Concentration Target mass flow Carrier mass flow Totalizer ...

Page 120: ...ent 76 Pulse output 76 Output frequency 76 Switch status 76 Heartbeat 1 112 Performing verification Year Month Day Hour AM PM Minute Verification mode External device information Start verification Progress Measured values Output values Status Overall result Verification results Date time Verification ID Operating time Overall result Sensor Sensor integrity ...

Page 121: ...equency value 71 Pulse simulation 71 Pulse value 72 Switch output simulation 72 Switch status 72 Simulation device alarm 72 Simulation diagnostic event 72 1 Order code for Application package option EB Heartbeat Verification and Monitoring see Special Documentation for the device 17 1 5 Expert menu Overview Expert menu Expert 34 Locking status 0004 74 Access status display 0091 Access status tooli...

Page 122: ...argraph value 1 0125 59 Decimal places 1 0095 69 Value 2 display 0108 59 Decimal places 2 0117 69 Value 3 display 0110 59 0 bargraph value 3 0124 59 100 bargraph value 3 0126 59 Decimal places 3 0118 70 Value 4 display 0109 59 Decimal places 4 0119 70 Display interval 0096 70 Display damping 0094 70 Header 0097 70 Header text 0112 70 Separator 0101 70 Backlight 0111 70 Diagnostic handling 78 Alarm...

Page 123: ...havior of diagnostic no 835 Assign behavior of diagnostic no 912 Assign behavior of diagnostic no 913 Assign behavior of diagnostic no 944 Assign behavior of diagnostic no 192 Assign behavior of diagnostic no 274 Assign behavior of diagnostic no 835 0678 Assign behavior of diagnostic no 392 Assign behavior of diagnostic no 592 Assign behavior of diagnostic no 992 Administration 72 Define access co...

Page 124: ...Target mass flow Carrier mass flow Totalizer 1 to 3 67 Totalizer value 1 to 3 75 Totalizer overflow 1 to 3 Output values 75 Output current 0361 1 to 76 Measured current 0366 1 to 76 Pulse output 0456 76 Output frequency 0471 76 Switch status 0461 76 System units 48 Mass flow unit 49 Mass unit 49 Volume flow unit 49 Volume unit 49 Corrected volume flow unit 49 Corrected volume unit 50 Density unit ...

Page 125: ...569 User volume factor 0568 User corrected volume text 0592 User corrected volume offset 0602 User corrected volume factor 0590 User density text 0570 User density offset 0571 User density factor 0572 User pressure text 0581 User pressure offset 0580 User pressure factor 0579 Process parameters 48 Flow damping Density damping Temperature damping Flow override Low flow cut off 63 Assign process var...

Page 126: ...ximum damping partial filled pipe det Measurement mode 51 Select medium 51 Select gas type 51 Reference sound velocity 51 Temperature coefficient sound velocity 51 External compensation 51 Pressure compensation 51 Pressure value 51 External pressure 51 External temperature Calculated values Corrected volume flow calculation Corrected volume flow calculation 66 External reference density 66 Fixed r...

Page 127: ...w offset Mass flow factor Volume flow offset Volume flow factor Density offset Density factor Corrected volume flow offset Corrected volume flow factor Reference density offset Reference density factor Temperature offset Temperature factor Calibration Calibration factor Zero point Nominal diameter C 0 C 1 to 5 Output submenu Output Current output 1 52 Assign current output 0359 53 Current span 035...

Page 128: ... 1 0366 76 Pulse frequency switch output 1 54 Operating mode 0469 54 Assign pulse output 0460 54 Value per pulse 0455 54 Pulse width 0452 54 Measuring mode 0351 Failure mode 0480 54 Pulse output 1 0456 76 Assign frequency output 0478 55 Minimum frequency value 0453 56 Maximum frequency value 0454 56 Measuring value at minimum frequency 0476 56 Measuring value at maximum frequency 0475 56 Measuring...

Page 129: ...7 Switch off value 0464 57 Assign status 0485 57 Switch on delay 0467 57 Switch off delay 0465 58 Failure mode 0486 58 Switch status 1 0461 76 Invert output signal 0470 54 Communication submenu Communication HART input Configuration Capture mode 7001 Device ID 7007 Device type 7008 Manufacturer ID 7009 Burst command 7006 Slot number 7010 Timeout 7005 Failure mode 7011 Failure value 7012 Input Valu...

Page 130: ... device variable code 0 7 Burst trigger mode Burst trigger level Min update period Max update period Information 87 Device revision 0204 88 Device ID 0221 88 Device type 0222 89 Manufacturer ID 0223 89 HART revision 0205 43 HART descriptor 0212 HART message 0216 HART date code 0202 Hardware revision 0206 Software revision 0224 HART date code Output 43 Assign PV 0234 43 Primary variable PV 0201 43 ...

Page 131: ...rver language MAC address IP address Subnet mask Default gateway Web server functionality Diagnostic event category Event category 046 Event category 140 Event category 274 Event category 441 Event category 442 Event category 443 Event category 830 Event category 831 Event category 832 Event category 833 Event category 834 Event category 835 Event category 862 Event category 912 Event category 913...

Page 132: ...67 Control Totalizer 1 to 3 0912 1 to 3 77 Preset value 1 to 3 0913 1 to 3 77 Failure mode 0901 67 Concentration Concentration unit User concentration text User concentration factor User concentration offset A 0 A 1 to 4 B 1 to 3 Diagnostics submenu Diagnostics 78 Actual diagnostics 0691 85 Timestamp Previous diagnostics 0690 85 Timestamp Operating time from restart 0653 85 Operating time 0652 85 ...

Page 133: ... 88 Order code 0008 88 Extended order code 1 to 3 0023 1 to 3 88 Configuration counter ENP version 0012 88 Min max values Reset min max values Electronic temperature Minimum value Maximum value Medium temperature Minimum value Maximum value Carrier pipe temperature Minimum value Maximum value Oscillation frequency Minimum value Maximum value Torsion oscillation frequency Minimum value Maximum valu...

Page 134: ...nimum value Maximum value Torsion oscillation damping Minimum value Maximum value Signal asymmetry Minimum value Maximum value Heartbeat 1 112 Progress Customer 2750 Location 2751 Performing verification Year 2846 Month 2845 Day 2842 Hour 2843 AM PM 2813 Minute 2844 Start verification 12127 Progress Status Overall result 12149 Verification results Date time 12142 ...

Page 135: ...electronic module I O module 12145 Heartbeat Monitoring Activate monitoring Monitoring results Sensor integrity Simulation Assign simulation process variable 1810 71 Value process variable 1811 71 Simulation device alarm 0654 72 1 Order code for Application package option EB Heartbeat Verification and Monitoring see the Special Documentation for the device ...

Page 136: ...ity 104 Design Measuring device 11 Design fundamentals Maximum measured error 102 Repeatability 102 Designated use 8 Device components 11 Device description files 43 Device documentation Supplementary documentation 7 Device locking status 74 Device name Sensor 14 Transmitter 13 Device repair 91 Device revision 43 Device type ID 43 Diagnostic information Design description 80 FieldCare 79 Light emi...

Page 137: ...s 20 Input 95 Inspection Received goods 12 Inspection check Connection 30 Installation 18 Installation conditions Down pipe 18 Mounting location 18 Orientation 19 Rupture disk 22 Sensor heating 22 System pressure 20 Thermal insulation 21 Vibrations 22 Installation dimensions 20 Interior cleaning 90 L Languages operation options 109 Low flow cut off 98 M Main electronics module 11 Maintenance tasks...

Page 138: ...submenu 66 Setup menu 48 Simulation submenu 70 System units submenu 48 Totalizer submenu 75 Totalizer 1 to 3 submenu 67 Web server submenu 37 Performance characteristics 100 Post connection check checklist 30 Post installation check 48 Post installation check checklist 24 Potential equalization 99 Power consumption 99 Power supply failure 99 Pressure Equipment Directive 110 Pressure loss 105 Press...

Page 139: ...4 Process variables 65 Supply voltage 99 System design Measuring system 95 see Measuring device design System integration 43 System pressure 20 T Technical data overview 95 Temperature range Medium temperature 104 Storage temperature 16 Terminal assignment 27 28 Terminals 99 Thermal insulation 21 Tools Electrical connection 26 Installation 24 Transport 16 Transmitter Connecting the signal cables 2...