Operation options
Magphant
26
Hauser
Operating and display
element
Meaning
4
2
1
3
limit
limit+error
A0040161
Relay functions
If all functions are operating correctly, the relay is energized. The relay is de-
energized as soon as an error or alarm occurs:
"Limit" switch position
The relay is de-energized and the red LED is lit if the limit value is exceeded or
undershot (this depends on the min./max. safety setting).
"Limit+error" switch position
The same function as the "limit" function but in addition: The relay is de-
energized if the flow velocity is greater than the measurable value of the
measuring device of if a device error occurs. The red LED flashes. "Error" has a
higher priority than "limit".
Factory setting
"Limit" switch position.
3
2
1
4
min.
max.
A0040162
Min./max. safety setting
"Min." switch position
The relay is de-energized if the signal drops below the limit value. The red
LED lights up.
"Max." switch position
The relay is de-energized if the signal exceeds the limit value. The red LED
lights up.
Factory setting
"Limit" switch position.
limits %
10
100
50
A0040165
Limit value setting
The limit value is defined as a % of the full scale value using this switch. It can
be set in increments of 10%, from 10% to 100%.
A0040167
Limit value or error indicator
LED is lit red
Limit value is reached.
LED flashes red
A0040166
Indicator for full scale setting
LED is lit green
The current flow is lower than the configured full scale value, i.e. I = ≥20 mA
1
2
3
4
5
m/s
A0040164
Full scale value scaling
Full scale value scaling can be adjusted continuously between 1 and 5 m/s via
this potentiometer.
Full scale setting:
The change from an unlit green LED to a lit green LED indicates that the full
scale value matches the current flow velocity, with the current output set to
20 mA.