Operation
Liquistation CSF48
108
Hauser
If Bottle change mode
Time
is selected:
Time interval
00-00:02 to 31-00:00
DD-HH:MM
Factory setting
00-01:00 DD-HH:MM
Set the time (days, hours and minutes) after which
the system should change to the next bottle.
Bottle synchronization
Options
• None
• 1. bottle change time
• 1. Time of bottle
number
Factory setting
None
None:
The time of sampling and bottle change are not
synchronized.
1. bottle change time:
Sampling starts with the first bottle.
Set the synchronization time.
1. Time of bottle number:
Each bottle is assigned to a specific fill time.
Set the synchronization time and the weekday.
Start condition
Options
• Immediate
• Date/time
Factory setting
Immediate
The sampling program can be started either
immediately or at a specific, configurable time.
If Start condition
Immediate
is selected:
Sample at start
Options
• Yes
• No
Factory setting
Yes
Yes:
The first sample is taken when the program is started.
No:
The system waits for the interval to elapse before the
first sample is taken.
If Start condition
Date/time
is selected:
Start date
01.01.2000 to 31.12.2099
Factory setting
DD.MM.YYYY
Set the start date for the sampling program. The
format depends on the option configured under
general settings.
Start time
00:00:00 to 23:59:59
Factory setting
HH:MM:SS (24h)
Set the time when the sampling program is started.
The format depends on the option configured under
general settings.
Stop condition
Options
• Program end
• Continuous
Factory setting
Program end
Program end:
The device stops sampling automatically once it has
run through the set program.
Continuous:
The device runs through the set program continuously
in an infinite loop. Do not forget to empty the bottles.
Path: Menu/Setup/Sampling programs/Setup program/New/Basic
Function
Options
Info