Levelflex FMP55 HART
Diagnostics and troubleshooting
Hauser
87
13.1.3 Parametrization errors
Parametrization errors for level measurements
Error
Possible cause
Remedial action
Measured value wrong
If measured distance(Setup
→ Distance) matches the real
distance:
Calibration error
• Check and adjust the
Empty
calibration
necessary.
• Check and adjust the
Full calibration
parameter (→ 131) if necessary.
• Check and adjust linearization if
necessary (
Linearization
submenu
If measured distance (Setup
→ Distance) does not match the real
distance:
An interference echo affects the
measurement.
Perform mapping (
Confirm distance
parameter (→ 135)).
No change of the measured
value when emptying/filling
the tank
An interference echo affects the
measurement.
Perform mapping (
Confirm distance
parameter (→ 135)).
Build-up at the probe.
Clean the probe.
Error in the echo tracking
Deactivate echo tracking: Expert
→ Sensor → Echo tracking → Evaluation
mode =
History off
).
The diagnostic message
Echo lost
appears after
switching on the supply
voltage.
Echo threshold too high.
Check the
Medium group
parameter
(→ 129).
If necessary select a more detailed
setting in the
Medium property
parameter.
Level echo suppressed.
Delete mapping and record new
mapping curve if required (
Record map
parameter (→ 137)).
Device displays a level when
the tank is empty.
Incorrect probe length
Carry out probe length correction
(
Confirm probe length
parameter
Interference echo
Carry out mapping over entire probe
while the tank is empty (
Confirm
distance
parameter (→ 135)).
Wrong slope of the level in
the entire measuring range
Wrong tank type selected.
Set
Tank type
correctly.
Parametrization errors for interface measurements
Error
Possible cause
Remedial action
Wrong slope of the measured
interface level
Wrong dielectric constant (DC value). Enter the correct dielectric constant (DC
value) of the upper medium (
DC value
parameter (→ 133)).
The measured values for the
interface and the total level
are identical
Echo threshold for the total level too
high due to a wrong dielectric
constant.
Enter the correct dielectric constant (DC
value) of the upper medium (
DC value
parameter (→ 133)).
If the interface layers are
thin, the total level jumps to
the interface level.
The thickness of the upper medium
is less than 60 mm (2.4 in).
Interface measurement is only possible
if the thickness of the interface is
greater than 60 mm (2.4 in).