Levelflex FMP55 HART
Operating menu
Hauser
175
Switch-off delay
Navigation
Setup → Advanced setup → Switch output → Switch-off delay
Prerequisite
•
Switch output function (→ 171)
Limit
•
Off
Description
Defines the delay applied before the output is switched off.
User entry
0.0 to 100.0 s
Factory setting
0.0 s
Failure mode
Navigation
Setup → Advanced setup → Switch output → Failure mode
Prerequisite
Switch output function (→ 171)
=
Limit
or
Digital Output
Description
Defines the state of the switch output in case of an error.
Selection
• Actual status
• Open
• Closed
Factory setting
Open
Additional information
Switch status
Navigation
Setup → Advanced setup → Switch output → Switch status
Description
Current status of the switch output.
Invert output signal
Navigation
Setup → Advanced setup → Switch output → Invert output signal
Description
'No' The switch output behaves as per its parameter setting. 'Yes' The switching behavior is
inverted as compared to its parameter setting.
Selection
• No
• Yes