Operating menu
Levelflex FMP55 HART
174
Hauser
t
t
B
A
C
D
A0015586
A
Switch-on value
B
Switch-off value
C
Output closed (conductive)
D
Output opened (non-conductive)
Switch-on delay
Navigation
Setup → Advanced setup → Switch output → Switch-on delay
Prerequisite
•
Switch output function (→ 171)
Limit
•
Off
Description
Defines the delay applied before the output is switched on.
User entry
0.0 to 100.0 s
Factory setting
0.0 s
Switch-off value
Navigation
Setup → Advanced setup → Switch output → Switch-off value
Prerequisite
Switch output function (→ 171)
=
Limit
Description
Defines the switch-off point. The output is opened if the assigned process variable falls
below this point.
User entry
Signed floating-point number
Factory setting
0
Additional information
The switching behavior depends on the relative position of the
Switch-on value
and
Switch-off value
parameters; description: see the
Switch-on value
parameter