Operating menu
Levelflex FMP55 HART
130
Hauser
Description
Select medium group.
Selection
• Others
• Water based (DC >= 4)
Factory setting
Others
Additional information
This parameter roughly specifies the dielectric constant (DC) of the medium. For a more
detailed definition of the DC use the
Medium property
parameter.
The
Medium group
parameter presets the
Medium property
parameter as follows:
Medium group
Medium property
Others
Unknown
Water based (DC >= 4)
DC 4 ... 7
The
Medium property
parameter can be changed at a later point of time. However,
when doing so, the
Medium group
parameter retains its value. Only the
Medium
property
parameter is relevant for the signal evaluation.
The measuring range may be reduced for small dielectric constants. For details refer
to the Technical Information (TI) of the respective device.
Empty calibration
Navigation
Setup → Empty calibration
Description
Distance between process connection and minimum level (0%).
User entry
Depending on the probe
Factory setting
Depending on the probe
Additional information
0%
E
E
0%
A0013177
44
Empty calibration (E) for interface measurements
In the case of interface measurements the
Empty calibration
parameter is valid for
both, the total and the interface level.