Levelflex FMP55 HART
Operating menu
Hauser
205
Factory setting
Off
Additional information
An active simulation is indicated by a diagnostic message of the
Function check (C)
category.
Value current output 1 to 2
Navigation
Expert → Diagnostics → Simulation → Value current output 1 to 2
Prerequisite
Current output simulation (→ 204)
On
Description
Defines the value of the simulated output current.
User entry
3.59 to 22.5 mA
Factory setting
3.59 mA
Additional information
The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Switch output simulation
Navigation
Expert → Diagnostics → Simulation → Switch output simulation
Description
Switch the simulation of the switch output on and off.
Selection
• Off
• On
Factory setting
Off
Switch status
Navigation
Expert → Diagnostics → Simulation → Switch status
Prerequisite
Switch output simulation (→ 205)
On
Description
Current status of the switch output.
Selection
• Open
• Closed
Factory setting
Open