Hardware lock
After Fieldgate has been commissioned, a local hardware lock can be set that prevents any
modifications to Fieldgate settings via Internet, GSM or Modem.
6.5.1 Activating the hardware lock
Note!
• You require local access to the Fieldgate to deactivate the lock!
Procedure
1 If not already selected, press
"Switch to Administration Mode"
and log in as administrator.
2 Press
Settings => Special,
then scroll down to
Miscellaneous Settings
:
3 Check the box
Enable Configuration Hardware Lock
, then press
Send
– The hardware lock is now enabled
6.5.2 Deactivating the hardware lock
Note!
• The service interface is not affected by the hardware lock and can always be used to access the
Fieldgate!
• The lock cannot be deactivated when the Fieldgate is booting - this causes a device reset.
The lock can be deactivated temporarily during normal operation by pressing the reset button for
one second, see Chapter 9.2. This allows access for five minutes, after which the lock is enabled
again. Pressing the reset button for 5 seconds enables the lock immediately.
The lock can be deactivated permanently by first temporarily unlocking it, then disabling it by
unchecking the
Enable Configuration Hardware Lock
box and pressing
Send
. Alternatively this
can be done via the Service Interface.