Fieldgate FXA520
12 Appendix
Hauser
101
12.2 XML data elements
Table 12-1 lists the XML data elements together with the type of information they carry. The XML
data is a structured document with a document header and body. The Fieldgate data is sandwiched
between two identifiers <xxx> and </xxx> which indicate the start and finish of the data element.
Data elements can be nested to form sections containing related information.
Element
Data Type
Description
<?xml version="1.0"
encoding="iso-8859-1"?>
Document header
<fieldgate ser="470009010A0"
tag="Hauser Fieldgate"
type="full"
devices="all">
tag field
Tag for fieldgate data<ser>:serial number fieldgate
<tag>: name fieldgate,
<type>: "full"/"partial" (short=1),
<devices>: "all /"single" (id=, tag=)
<rev_xml>
string
Document Revision
<time>
timestamp
Current fieldgate time (UTC time)
<timezone>
unsigned16
Timezone (timeoffset to utc in minutes)
<ff_version>
string
Hardware and software revision
<gsmp>
string
GSM-Provider
<gsms>
string
Signal quality GSM Signal
<gsmti>
timestamp
Timestamp
<os_version>
string
operating system version
<conf>
string
hardware configuration Fieldgate
<ip>
string
IP address of Fieldgate
<device id="_4..20mA-1 "
tag="Levelflex FMPP40"
type="INTRN">
tag field
device data: <id>: Unique-ID device,
<tag>: Tag des Gerätes
<type>: "INTRN"
<hlsts1>, <hlsts2>,<hlsts3>,<hlsts4> string
Limit value status, channels 1 - 4: PV, SV, TV and QV
<hltime1>, <hltime2>, <hltime3>,
<hltime4>
Timestamp
Timestamp change of limit value status, channels 1 - 4:
PV, SV, TV and QV
<chn>, <chn2>, <chn3>, <chn4>
integer
Channel: 01 = HART channel 1, 10 = HART channel 2,
11 = RS485
<ctime>, <ctime2>, <ctime3>,
<ctime4>
Timestamp
Timestamp of first command 000 (HART)
(brings: Expanded Device Type Code, Revision Levels, Device ID)
<v1>, <v2>, <v3>, ´<v4>
float
Process variable, channels 1 - 4: PV, SV, TV and QV
<u1>, <u2>, <u3>, <u4>
float
Unit of process variable, channels 1 - 4: PV, SV, TV and QV
<vstslvl>
integer
Device error
0: OK
1: Warning
2: Error (according to HART6-Spec)
<vsts>
string
Answer code and fault status(hex)
<vtime>
Timestamp
Timestamp of command 000
<v1_100>
float
Primary variable percent of range
<v1_lc>
float
Primary variable loop current
<stsext>
string
Status externer Module (FXZ520)
<fnum>
float
Expanded Device type Code des Gerätes (HART)
<datecode>
float
Herstellungsdatum des Gerätes (HART)
<desc>
string
Beschreibung der Gerätetyp (HART)
<tag>
string
Messstellungbezeichnung des Gerätes
<msg>
string
User text (HART
<serno>
integer
Seriennummer des Gerätes (HART)
<hwrev>
integer
Hardware-Revision des Gerätes (HART)
<swrev>
integer
Software-Revision des Gerätes (HART
<devrev>
integer
Revision des Gerätes (HART
<cmdrev>
integer
Kommando-Revision des Gerätes (HART
<preamble>
integer
Number of preambles(HART
<stime>
timestamp
Timestamp of cmd000(HART)
(brings: Expanded Device Type Code, Revision Levels, Device ID)
<pid>
integer
Product idenitfication number (HART
<type>
string
Type of device (INTRN = data internal, HART = data from device)
<dev>
string
Device designation