6 Configuring the Fieldgate
Fieldgate FXA520
62
Hauser
Data Logging
6 If your Fieldgate has a DAT module installed and you wish to access the data it contains, see
Chapter 8.2, scroll down to the Data Logging dialog
7 Enter the parameters you require – their significance is described in the table below:
– Press
"Send"
to download the user parameters to the Fieldgate.
Note!
• Fieldgate can log only a limited number of records, see Chapter 8.2.
6.3.5 Input
Input
allows you to configure the overview page, i.e. to:
• select the measured values to be displayed from HART devices
• set warning and alarm limits on the displayed values
• scale and assign engineering units to connected 4-20 mA devices
• assign explanatory text to connected binary devices
• set up the e-mail response to sensor errors
The various functions are described in Chapter 6.4, Overview
Parameter
Description
Data Logging Cycle
Time
Sets the cycle time for storage of data to the history log (DAT module)
– None: no DAT present
– Use Scan Cycle: data saved on every scan
– 1h to 7 d: data saved after elapse of selected time interval
– each hour/00:00 etc: data saved at specified time(s)
Log Events
Check the box to save data on a Fieldgate event - a scan is made prior to saving