12 Appendix
Fieldgate FXA520
102
Hauser
Table 12-1: XML data elements
<man>
string
Device manufacturer
<unid>
string
Unique identifier of device
<param>
(only a example)
<dch>, <dch2>, <dch3>, <dch4>
boolean
1: Process value in overview, channels 1 - 4: PV, SV, TV and QV
<p4>
float
Output Value at 4.00mA Input Current (internal sensor only)
<p20>
float
Output Value at 20.00mA Input Current (internal sensor only)
<r>
boolean
1: Alarm mail on sensor error
<i>, <i2>, <i3>, <i4>
boolean
1: Alarm mail on leaving limits, channels 1 - 4:
PV, SV, TV and QV
<o>, <o2>, <o3>, <o4>
boolean
1: Alarm mail on returning to limits, channels 1 - 4:
PV, SV, TV and QV
<si>, <si2>, <si3>, <si4>
boolean
1: Send SMS on entering limits (PV)
<so>, <so2>, <so3>, <so4>
boolean
1: Send SMS on leaving limits (PV)
<t1ch>, <t1ch2>, <t1ch3>, <t1ch4> string
Additional text information line 1, channels 1 - 4:
PV, SV, TV and QV
<t2ch>, <t2ch2>, <t2ch3>, <t2ch4> string
Additional text information line 2, channels 1 - 4:
PV, SV, TV and QV
<lo>, <lo2>, <lo3>, <lo4>
float
Low limit, channels 1 - 4: PV, SV, TV and QV
<ll>, <ll2>, <ll3>, <ll4>
float
Low Low limit, channels 1 - 4: PV, SV, TV and QV
<hi>, <hi2>, <hi3>, <hi4>
float
High limit, channels 1 - 4: PV, SV, TV and QV
<hh>, <hh2>, <hh3>, <hh4>
float
High High limit, channels 1 - 4: PV, SV, TV and QV
<alt>, <alt2>, <alt3>, <alt4>
float
Wertangabe für Grenzwertänderung Kanal 1 - 4;
PV, SV, TV und QV
<lt>, <lt2>, <lt3>, <lt4>
string
Linearization table, channels 1 - 4: PV, SV, TV and QV
<val>, <val2>, <val3>, <val4>
float
Last value stored in memory
<max>, <max2>, <max3>, <max4> float
Max. value reached by process value during operation,
channels 1 - 4: PV, SV, TV and QV
<min>, <min2>, <min3>, <min4> float
Min. value reached by process value during operation,
channels 1 - 4: PV, SV, TV and QV
<hy>, <hy2>, <hy3>, <hy4>
float
Hysteresis for re-entering limits, channels 1 - 4:
PV, SV, TV and QV
<swl>, <swl2>, <swl3>, <swl4>
float
Switching level for status display, channels 1 - 4:
PV, SV, TV and QV
<swsts>, <swsts2>, <swsts3>,
<swsts4>
integer
Text display switching status, channels 1 - 4: PV, SV, TV and QV
1 = " uncovered" / "covered"
2 = "covered" / "uncovered"
3 = "on" / "off"
4 = "off" / "on"
5 = "empty" / "full"
6 = "full" / "empty"
7= "good" / "bad"
8= "bad" / "good"
<_t>
string
Device name/Tag (internal sensors only)
<_h>
boolean
1: Hide device from device overview
<_u>
string
Output unit (internal analog sensor only)
Element
Data Type
Description