background image

DR-GW1000

DIN RAIL MOUNTED ETHERNET GATEWAY

DR-GW1000 is a DR-Link protocol compliant 

Ethernet gateway designed for use with Direct 

Series lighting control modules and is capable of 

auto acquiring online devices within the range and 

monitoring and reporting any operation error of the 

lighting system.

 

• 

Designed for standard 35mm DIN rail installation [Space Occupa-

tion: 4P (per P:18mm)].

• 

Online upgrading.

• 

Communication through DR-Link interface and capaple of auto 

acquiring online devices and monitoring and reporting operation 

errors. 

• 

Two DR-Link interfaces connects up to 63 DR-Link devices.

  

• 

An extended control system can be set up through ethernet connec-

tion with IPad, Andriod touch panel or AMX controller.

• 

Data import/export.

• 

Local or remote data download through Ethernet connector. 

1. 

LED Indicators and Control Buttons:

• 

POWER: indicates status of power supply.

• 

LINK: indicates status of control interface. When solid on, the 

control interface is operating correctly; When blinking, a fault 

appears to the control interface. 

• 

RESET: resets IP to factory default (192.168.1.230:6000). 

Press for 6 seconds and wait till the LINK LED stops blinking. 

Then the resetting is successful.

• 

CLEAR: clears all setting data from the module. Press for 6 

seconds and wait till the LINK LED stops blinking. Then all 

the setting data are successfully erased. 

2. 

DR-Link Interface: 24V, G, A, B.

3. 

RS232 Interface: uses a Phoenix terminal to connect a RS232 

device. Port parameter: 115200,n,8,1.

4. 

Control Keypad Interface: uses a RJ45 connector (with LED indica-

tors) to connect a control keypad. The cable connected should be 

wired to 586B standard. 

5. 

Electrical box Interface: uses a RJ45 connector (with LED indica-

tors) to connect an electrical box. The cable connected should be 

wired to 586B standard.

6. 

ETHERNET Interface: uses a RJ45 connector (with LED indicators) 

to connect a router. The cable connected should be wired to 586B 

standard. The two ETHERNET connectors can not be used simulta-

neously. Please choose only one of the two to connect. 

FEATURES

STRUCTURE

SPECIFICATIONS

Power supply

DC 24V 90 mA

Control interface

2 × DR-Link

Ethernet

1 × RJ45 connector (with LED indicators)

Cascade connection

1 × RJ45 connector (with LED indicators)

Control keypad

1 × RJ45 connector (with LED indicators)

LED indicators

1 × POWER, 1 × ETHERNET, 1 × LINK

Connectivity

Support up to 63 DR-Link devices

Control buttons

1 × RESET, 1 × CLEAR

Downloading

1 × Ethernet connector

Operation temperature / RH

0˚C - 45˚C / 20% - 93% RH

Storage temperature / RH

-40˚C - +55˚C / 10% - 93% RH

Dimensions (L x W x H)

72 mm × 98 mm × 68 mm (4P)

Weight

190 g/pcs

ETHERNET

4

3

6

6

2

2

5




电箱级联




1

DIRECT SERIES LIGHTING CONTROL MODULE

ETHERNET

68

98

72

measured in mm