6 Configuring the Fieldgate
Fieldgate FXA320
69
Hauser
6.4.5
Sensor error
A sensor error occurs when the output signal generated by the measuring device lies outside the
normal operating range of 4 mA to 20 mA for analog inputs or –3V to +5 V/15V to +30V for binary
inputs. The Web server responds to this condition by displaying ERROR or WARNING as status. An
e-mail is sent only when the device is in ERROR condition and the Alarm Mail box in the Sensor
Error dialog has been checked, see Table 6-11.
Table 6-11: Behaviour of analog device status and limit status for measured values outside range limits
The sensor error setup dialog for both analog and digital inputs is shown below. The significance of
the parameters is described in Table 6-12.
Sensor error setup
Table 6-12: Sensor error parameters
Output signal
≤
3.6 mA or
≥
21 mA (NAMUR limits)
3.6 mA to 3.8 mA/21.5 mA to 21 mA
Device Status
ERROR
WARNING
Response
Alarm e-mail sent if box checked
No e-mail sent
Parameter
Description
Alarm mail/SMS on
sensor error
Click to activate corresponding e-mail or SMS:
– For sensor errors, see Table 6-11 for further explanation.
Send
Press to register your changes in the Fieldgate.
Reset
Press to discard any changes made since the previous send.