12.2 XML data elements
Table 12-1 lists the XML data elements together with the type of information they carry. The XML
data is a structured document with a document header and body. The Fieldgate data is sandwiched
between two identifiers <xxx> and </xxx> which indicate the start and finish of the data element.
Data elements can be nested to form sections containing related information.
Element
Data Type
Description
<?xml version="1.0"
encoding="iso-8859-1"?>
Document header
<fieldgate ser="470009010A0"
tag="Hauser Fieldgate"
type="full"
devices="all">
tag field
Header for Fieldgate data <ser>:serial number fieldgate
<tag>: name fieldgate
<type>: "full"/"partial" (short=1),
<devices>: "all /"single" (id=, tag=)
<rev_xml>
string
Document Revision
<time>
timestamp
Current fieldgate time (UTC time)
<timezone>
unsigned16
Timezone (timeoffset to utc in minutes)
<ff_version>
string
Hardware and software revision
<gsmp>
string
GSM provider
<gsms>
string
Signal quality GSM Signal
<gsmti>
timestamp
Timestamp
<os_version>
string
Operating system version
<conf>
string
Hardware configuration Fieldgate
<ip>
string
IP address of Fieldgate
<device id="4...20 mA-1"
tag="Tank 1"
type="INTR">
tag field
Header for device data:
<id>: Unique-ID device, 4...20 mA-x, BINARY-x
<tag>: Tagname device
<type>:"INTRN"
<vtime>
Timestamp
Timestamp
<tag>
string
Device tag
<hlsts1>
string
Limit value status of PV
<hltime1>
Timestamp
Timestamp change of limit value status of PV
<v1>
float
Process variable (PV)
<u1>
float
Unit of process variable (PV)
<vstslvl>
integer
Device status
0: OK
1: Warning
2: Error
<vsts>
string
Response code & field device status (hex)
<type>
string
Type of device (INTRN = data internal)
<dev>
string
Device designation
<man>
string
Device manufacturer
<unid>
string
Unique identifier of device
<param>
Header for parameter data
<dch>
boolean
1: Process variable (PV) in overview
<p4>
float
Output value at 4.00 mA input current (internal sensor only)
<p20>
float
Output value at 20.00 mA input current (internal sensor only)
<r>
boolean
1: Send alarm mail on sensor error
<i>
boolean
1: Send alarm mail on entering limits (PV)
<o>
boolean
1: Send alarm mail on leaving limits (PV)
<si>
boolean
1: Send SMS on entering limits (PV)
<so>
boolean
1: Send SMS on leaving limits (PV)
<t1ch>
string
Additional text information line 1 (PV)
<t2ch>
string
Additional text information line 2 (PV)
<lo>
float
Low limit for process value (PV)
<ll>
float
Low low limit for process value (PV)
<hi>
float
High limit for process value (PV)
<hh>
float
High high limit for process value (PV)
<alt>
float
Value for rate of change limit on process value (PV)
<atime>
integer
Time for rate of change limit on process value (PV)
<cnho>
integer
Counter hold time = (chno +1)x 50 ms