Fieldgate FXA320
5 Commissioning
Hauser
50
5.6.2
Mail Setup
Configure the "Mail Setup" settings in order to send emails.
NOTE!
• Fieldgate only supports the "Simple Mail Transfer Protocol" (SMTP) to send emails.
• The method SMTPS for secure communication in e-mail transport via SMTP over SSL/TLS is
not supported by Fieldgate.
• Please consider when selecting the e-mail provider that the SMTP protocol is supported.
Encryption /authentication via SMTPS (SSL/TLS) is not supported by Fieldgate.
Procedure
1 If not already active, press
Switch to Administrator Mode => Settings
=> Message
– Scroll down to reveal the
Mail Setup
page.
– Enter your settings and confirm with
Send
.
Mail setup
Parameter
Description
SMTP Gateway
Enter the IP address or URL of your e-mail server here:
– Note: if no SMTP server is entered, Fieldgate will try to send the e-mail directly to the
server used by the receiver. In this case, the e-mails are mostly classified as spam.
SMTP User Name
If authentication is required for the specified SMTP Gateway, enter the user name here:
– Leave blank if no authentication is requested or no SMTP Gateway is used.
SMTP Password
If authentication is required for the specified SMTP Gateway, enter the password here:
– Leave blank if no authentication is requested or no SMTP Gateway is used.
Sender Address
Enter the sender address of the Fieldgate here, e.g. [email protected]:
– With some providers, the e-mail address of the account holder must be specified as the
sender address. No mails will be accepted from other sender addresses.
– Where the sender address is freely selectable, choose a serious address to avoid trouble
with spam filters.
Address Service Alarm
Mails
Enter the recipient of the service alarm mails here, e.g. [email protected].
Address Limit Alarm Mails
Enter the recipient of the limit alarm mails here, e.g. [email protected]:
– Alarm notifications are sent in accordance with the settings made in the "Message on
Limit" column of the device details page, see chap. 6.4.
Address Measurement
Mails
Enter the recipient of the measurement mails here, e.g. [email protected]:
– Measurement notifications are sent in accordance with the settings of the parameters
below.
Periodic Measurement
Mails
Select period for sending mails from dropdown menu.
Format Measurement Mails
Select format for sending mails from dropdown menu:
– XML is required if the e-mails are to evaluated by the Fieldgate Data Access software
and/or SupplyCare.