9 Trouble-Shooting
Hauser
92
9.3
Troubleshooting on no connection
1 Is the Link LED lit on the Fieldgate?
–
Yes, proceed with point 2
–
No, check the cable or connection to Fieldgate and PC/Network
2 Is the Link LED of the PC network card lit?
–
Yes, proceed with point 3
–
No, check the cable or connection to Fieldgate and PC/Network
3 Open the DOS prompt "
Start => Run => cmd
"
4 Enter "
ping 192.168.252.1
". Do you get the answer 192.168.252.1 Bytes=32...
–
Yes. The connection is OK.
Check your browser settings (If a proxy server is used try to bypass the
IP-address 192.168.252.1).
–
No. There is no connection to the Fieldgate.
5 Check if Fieldgate’s IP and Subnet mask are in the same network as your PC:
–
No: Reconfigure the gateway address.