Function parameter schedule graph
28
F6.05 Triangle wave rising
time
0.0
~
98(%) (Triangle wave rising time)
0.1(%) 50.0(%)
○
F6.06 Traverse
preset
frequency
0.00
~
400.00Hz 0.01Hz
0.00Hz
○
F6.07 Traverse
preset
frequency latency time
0.0
~
6000s 0.1s
0.0s
○
F7
-
Frequency provision function parameter group
Function
code
Name
Set range
Min
unit
Factory
default
modifi
cation
F7.00
~
F7.03
Reserved
F7.04 CCI Minimum provision
0.00
~
F7.06 0.01V
0.00V
○
F7.05 Corresponding freq. to CCI
minimum provision
0.00
~
Upper limit frequency
0.01
Hz
0.00Hz
○
F7.06 CCI
max.
provision
0.00
~
10.00V 0.01V
9.9V
○
F7.07 Corresponding freq. to CCI
max. provision
0.00
~
Upper limit frequency
0.01
Hz
50.00Hz
○
F7.08
~
F7.17
Reserved
F8
-
Motor and vector control function parameter group
Function
code
Name
Set range
Min
unit
Factory default
modifi
cation
F8.00 Reserved
F8.01 Motor rated voltage
1
~
999V
1V
Depend on device type
×
F8.02 Motor rated current
0.1
~
999.9A
0.1A
Depend on device type
×
F8.03 Motor rated frequency 1.00
~
400.0Hz
0.01Hz
Depend on device type
×
F8.04 Motor rated speed
1
~
9999r/min
1r/min
Depend on device type
×
F8.05 Motor
pole
2
~
14
2
Depend on device type
×
F8.06 Motor rated power
0.1
~
999.9KW
0.1
Depend on device type
×
F8.07
~
F08.17
Reserved
F9
-
Protection function parameter
Function
code
Name
Set range
Min
unit
Factory
default
modifi
cation
F9.00 Reserved
F9.01 Failure
self-restoration
times
0
~
10
0 means: No self-restoration function.
Noted: Self-restoration function is ineffective
to failure protection caused by overload and
over heat.
1 0 ×
F9.02 Failure
self-restoration 0.5
-
20.0S 0.1S
5.0S
×
ENC