Function parameter schedule graph
29
interval
F9.03 Motor overload protection
mode selection
0: No action
1: Inverter cut off output at once
1 1 ×
F9.04 Motor overload protection
coefficient
20.0
~
120.0
(
%
)
0.1(%)
100.0
(%)
×
F9.05 Overload alarm checkout
level
20
~
200
(
%
)
1(%)
130(%)
○
F9.06 Overload alarm delay time 0.0
~
20.0s 0.1s
5.0s
○
F9.07 Overvoltage stall selection 0: Banned
1: Allowed
1 1 ×
F9.08 Stall overvoltage point
120
~
150
(
%
)
1(%)
140(%)
○
F9.09 Automatic
current
limiting level
110
~
200
(
%
)
1(%)
150(%)
×
F9.10 Frequency
descending
rate during current
limiting
0.00
-
99.99Hz/s 0.01Hz
/s
10.00Hz
/s
○
F9.11 Automatic
current
limiting action selection
LED Units digit
0
:
Invalid
1
:
Valid
LED Tens digit
:
Input loss phase detection
0
:
Invalid
1
:
Valid
1 00 ×
Fd
-
Failure record function parameter
Function
code
Name
Set range
Min
unit
Factory
default
modifi
cation
Fd.00 Previous one failure record
Previous one failure record
1
0
*
Fd.01 Previous two failure record
Previous two failure record
1
0
*
Fd.02 Previous three failure record
Previous three failure record
1
0
*
Fd.03 Previous four failure record
Previous four failure record
1
0
*
Fd.04 Previous five failure record
Previous five failure record
1
0
*
Fd.05 Previous six failure record
Previous six failure record
1
0
*
Fd.06 Set freq. at previous failure
Set freq. at previous failure
0.01Hz
0
*
Fd.07 Output freq. at previous failure
Output freq. at previous failure
0.01Hz
0
*
Fd.08 Output current at previous failure
Output current at previous failure
0.1A
0
*
Fd.09 Output volt. at previous failure
Output volt. at previous failure
1V
0
*
Fd.10 DC bus-bar vlot. at previous failure DC bus-bar vlot. at previous failure
1V
0
*
Fd.11 Load motor speed at previous
Load motor speed at previous failure
1(r/m)
0
*
Fd.12 Module temp. at previous failure
Module temp. at previous failure
1
℃
0 *
Fd.13 Input end state at previous failure
Input end state at previous failure
0
*
Fd.14 Accu. runtime at previous failure
Accu. runtime at previous failure
0
*
FF
-
Code and manufacturer function parameter
Function
code
Name
Set range
Min
unit
Factory
default
modifi
cation
FF.00 User
password
0000
~
9999 1
0000
×
FF.01 Manufacturer
password
0000
~
9999 1
0000
×
ENC