Function parameter schedule graph
19
F0.07 Accelerating
decelerating time unit
0: Second
1: Minute
1 0 ×
F0.08 Acce time 1
0.1
~
6000.0 0.1
20.0
○
F0.09 Dece time 1
0.1
~
6000.0 0.1
20.0
○
F0.10 Upper limit freq.
Lower limit freq.
~
400.00Hz
0.01Hz 50.00Hz
×
F0.11 Lower limit freq.
0.00
~
Upper limit freq.
0.01Hz 0.00Hz
×
F0.12 Lower limit freq.
run mode
0: Run at lower limit freq.
1: Stop running
1 0 ×
F0.13 Torque
boost
mode
0: Manual boost
1: Automatic boost
1 0
○
F0.14 Torque
boost
0.0
~
20.0
(
%
)
0.1(%)
4.0(%)
○
F0.15 V/Fcurve setting
0: Constant torque curve
1: Degressive torque curve 1
(
The 2.0nd power
)
2: Degressive torque curve 2
(
The 1.7th power
)
3: Degressive torque curve 3
(
The 1.2th power
)
4: End-user sets VF curve himself (determined by
F2.37~F2.44)
F2.37 VF Freq. value 0
F2.38 VF voltage value 0
F2.39 VF Freq. value 1
F2.40 VF voltage value 1
F2.41 VF Freq. value 2
F2.42 VF voltage value 2
F2.43 VF Freq. Value 3
F2.44 VF voltage 3
Remark: VF frequency and voltage can’t be 0or
maximum
1
0.01Hz
0.01%
0.01Hz
0.01%
0.01Hz
0.01%
0.01Hz
0.01%
0
0.50Hz
2.00%
20.00Hz
38.00%
25.00Hz
48.00%
40.00Hz
80.00%
×
F0.16 Reserved
F1-Start-up, stop, Brake function parameter group
Function
Code
Name
Set Range
Unit
Factory
default
Modifi
-cation
F1.00 Start-up run mode
0: Start at start-up freq.
1: First brake,then start at start-up freq.
2: Reserved
1 0 ×
F1.01 Start-up
freq.
0.0
~
10.00Hz 0.01Hz
0.00Hz
○
F1.02 Start-up
freq.duration
0.0
~
20.0S 0.1s
0.0s
○
F1.03 Zero freq. DC braking volt.
0
~
15
(
%
)
1
0
○
F1.04 Zero freq. DC braking time
0.0
~
20.0S 0.1s
0.0s
○
F1.05 Stop mode
0: Dec stop
1: Free stop
2: Dec
+
DC brake stop
1 0 ×
F1.06 DC brake initiative freq.
when stop running
0.0
~
15.00Hz 0.01Hz
0.00Hz
○
F1.07 DC brake time when stop
running
0.0
~
20.0s 0.1s
0.0s
○
F1.08 DC brake voltage when stop
running
0
~
15
(
%
)
1
0
○
ENC