CG Drives & Automation 01-6142-01r0
Technical Data
53
8.
Technical Data
8.1
Electrical specifications related to model
Emotron FLD - IP20/21 version
* Available during limited time and as long as allowed by drive temperature.
Emotron FLD - IP54 version
* Available during limited time and as long as allowed by drive temperature.
Table 22
Typical motor power at mains voltage 230, 400 and 460V. AC drive main voltage range 230 - 480 V.
Model
Max.
output
current
[A]*
Normal duty
(120%, 1 min every 10 min)
Frame size
Rated
current
[A]
Power
@230V
[kW]
Power
@230V
[HP]
Power
@400V
[kW]
Power
@460V
[HP]
FLD48-025-20
30
25
5.5
7.5
11
15
C2
FLD48-030-20
36
30
7.5
10
15
20
FLD48-036-20
43
36
7.5
10
18.5
25
FLD48-045-20
54
45
11
15
22
30
FLD48-058-20
68
58
15
20
30
40
FLD48-072-20
86
72
18.5
25
37
50
D2
FLD48-088-20
106
88
22
30
45
60
FLD48-105-20
126
105
30
40
55
75
FLD48-142-20
170
142
37
50
75
100
E2
FLD48-171-20
205
171
45
60
90
125
FLD48-205-20
246
205
55
75
110
150
F2
FLD48-244-20
293
244
75
100
132
200
FLD48-293-20
352
293
90
125
160
250
Table 23
Typical motor power at mains voltage 230, 400 and 460 V. AC drive main voltage range 230 - 480 V.
Model
Max.
output
current
[A]*
Normal duty
(120%, 1 min every 10 min)
Frame
size
IP
klass
Rated
current
[A]
Power
@230V
[kW]
Power
@230V
[HP]
Power
@400V
[kW]
Power
@460V
[HP]
FLD48-003-54
3.0
2.5
0.37
0.5
0.75
1
B
IP 54
wall
mounted
FLD48-004-54
4.8
4.0
0.75
1
1.5
2
FLD48-006-54
7.2
6.0
1.1
1.5
2.2
3
FLD48-008-54
9.0
7.5
1.5
2
3
3
FLD48-010-54
11.4
9.5
2.2
3
4
5
FLD48-013-54
15.6
13.0
2.2
3
5.5
7.5
FLD48-018-54
21.6
18.0
4
5
7.5
10
FLD48-026-54
31
26
5.5
7.5
11
15
C
FLD48-031-54
37
31
7.5
10
15
20
FLD48-037-54
44
37
7.5
10
18.5
25
FLD48-046-54
55
46
11
15
22
30
FLD48-061-54
73
61
15
20
30
40
D
FLD48-074-54
89
74
18.5
25
37
50
FLD48-090-54
108
90
22
30
45
60
E
FLD48-109-54
131
109
30
40
55
75
FLD48-146-54
175
146
37
50
75
100
FLD48-175-54
210
175
45
60
90
125
FLD48-210-54
252
210
55
75
110
150
F
FLD48-228-54
300
228
55
75
110
200
FLD48-250-54
300
250
75
100
132
200