CG Drives & Automation, 01-6142-01r0
Installation
23
3.3
Connection of motor and
mains cables for larger
frame sizes
IP54 - FLD 48-090 to 250 (Frame sizes E - F) and
FLD 69-090 to 200 (Frame size F69)
Emotron FLD48-090 and up, Emotron FLD69-
090 and up
To simplify the connection of thick motor and mains cables
to the AC drive, the cable interface plate can be removed.
Fig. 35 Connecting motor and mains cables.
1. Remove the cable interface plate from the AC drive
housing.
2. Put the cables through the glands.
3. Strip the cable according to Table 13.
4. Connect the stripped cables to the respective mains/
motor terminal.
5. Fix the clamps on appropriate place and tighten the
cable in the clamp with good electrical contact to the
cable screen.
6. Put the cable interface plate in place and secure with the
fixing screws.
Cable interface
Clamps for screening
Mains cable
DC+, DC-, R (optional)
Motor cable