54
Technical Data
CG Drives & Automation 01-6142-01r0
Emotron FLD 2.0 - IP54 version (Model 69-250 and up also available as IP20)
* Available during limited time and as long as allowed by drive temperature.
Table 24
Typical motor power at mains voltage 525, 575 and 690 V.
AC drive main voltage range, for 52: 440 - 525 V and for 69: 500 - 690 V.
Model
Max.
output
current
[A]*
Normal duty
(120%, 1 min every 10 min)
Frame size
IP
class
Rated
current
[A]
Power
@525V
[kW]
Power
@575V
[HP]
Power
@690V
[kW]
FLD52-003-54
3.0
2.5
1.1
-
-
B
IP 54
wall
mounted
FLD52-004-54
4.8
4.0
2.2
-
-
FLD52-006-54
7.2
6.0
3
-
-
FLD52-008-54
9.0
7.5
4
-
-
FLD52-010-54
11.4
9.5
5.5
-
-
FLD52-013-54
15.6
13.0
7.5
-
-
FLD52-018-54
21.6
18.0
11
-
-
FLD52-026-54
31
26
15
-
-
C
FLD52-031-54
37
31
18.5
-
-
FLD52-037-54
44
37
22
-
-
FLD52-046-54
55
46
30
-
-
FLD52-061-54
73
61
37
-
-
D
FLD52-074-54
89
74
45
-
-
FLD69-090-54
108
90
55
75
90
F69
FLD69-109-54
131
109
75
100
110
FLD69-146-54
175
146
90
125
132
FLD69-175-54
210
175
110
150
160
FLD69-200-54
240
200
132
200
200