3.4
Cable specifications
3.4.1 Stripping lengths
Fig. 3.4.2 indicates the recommended stripping lengths for
motor and mains cables.
Fig. 36 Stripping lengths for cables
* With cable shoe for M6 screw
**Valid when brake chopper electronics are built in
Table 12
Cable specifications
Cable
Cable specification
Mains
Power cable suitable for fixed installation for the
voltage used.
Motor
Symmetrical three conductor cable with
concentric protection (PE) wire or a four
conductor cable with compact low-impedance
concentric shield for the voltage used.
Control
Control cable with low-impedance shield,
screened.
(06-F45-cables only)
Motor/Brake
Mains
Table 13
Stripping lengths for mains, motor, brake and earth cables
Model
Frame
size
Mains cable
Motor cable
Brake cable
Earth cable
a
mm
(in)
b
mm
(in)
a
mm
(in)
b
mm
(in)
c
mm
(in)
a
mm
(in)
b
mm
(in)
c
mm
(in)
a
mm
(in)
b
mm (in)
FLD##003 - 018
B
90
(3.5)
10
(0.4)
90
(3.5)
10
(0.4)
20
(0.8)
90
(3.5)
10
(0.4)
20
(0.8)
90
(3.5)
10 (0.4)
FLD##026 – 046
C
150
(5.9)
14
(0.2)
150
(5.9)
14
(0.2)
20
(0.8)
150
(5.9)
14
(0.2)
20
(0.8)
150
(5.9)
14 (0.2)
FLD48-025 – 058
C2
65
(2.7)
18
(0.7)
65
(2.7)
18
(0.7)
36
(1.4)
65
(2.7)
18
(0.7)
36
(1.4)
65
(2.7)
M6 screw*
FLD##061 – 074
D
110
(4.3)
17
(0.7)
110
(4.3)
17
(0.7)
34
(1.4)
110
(4.3)
17
(0.7)
34
(1.4)
110
(4.3)
17 (0.7)
FLD48-072 – 105
D2
92
(3.6)
18
(0.7)
92
(3.6)
18
(0.7)
36
(1.4)
92
(3.6)
18
(0.7)
36
(1.4)
92
(3.6)
M6 screw*
FLD##090 - 175
E
173
(6.8)
25 (1)
173
(6.8)
25 (1)
41
(1.6)
173
(6.8)
25 (1)
41
(1.6)
173
(6.8)
25 (1)
40 (1.6)**
FLD48-142 – 171
E2
FLD48-205 – 293
F2
178 (7)
32
(1.3)
178 (7)
32
(1.3)
46
(1.8)
178 (7)
46
(1.8)
178 (7)
32 (1.3)
40 (1.6)**
FLD48-210 – 250
FLD69-090 – 200
F