20
Installation
CG Drives & Automation, 01-6142-01r0
Fig. 28 Mains and motor connections model 48-072 to
48-105, frame size D2.
Fig. 29 Mains and motor connections model 48-142 to 48-
293 (Size E2 and F2) (principle drawing).
Fig. 30 Mains and motor connections model 48-142 to 48-
293 (Size E2 and F2) with the optional terminals for
DC-,DC+ and Brake (principle drawing)
Fig. 31 Wiring example showing Protective earth, Motor earth
and Brake Resistor connection
L1 L2 L3
DC- DC+
R U V W
PE
M
ai
ns
M
ot
or
for brake resistor
cables (option)
Strainrelief and EMC clamp
also for screen connection
of cables
Strainrelief and EMC clamp
PE
M
ot
or
M
ai
ns
Strainrelief and EMC clamp
also for screen connection
of cables
Table 11
Mains and motor connections
L1,L2,L3
PE
Mains supply, 3 -phase
Safety earth (protected earth)
U, V, W
Motor earth
Motor output, 3-phase
DC-,DC+,R
Brake resistor, DC-link
connections (optional)
NOTE: The Brake and DC-link Terminals are only fitted if
the DC+/DC- option or Brake Chopper Option is built-in.
PE
DC+
DC-
R
PE
M
ot
or
M
ai
ns
Strainrelief and EMC clamp
also for screen connection