88
GB
GB
Menù
label
Par Label
Descrizione
U.
m.
Range
Default C-TH
PW
Address
(Base 0)
min
max
USYS
200
Room set point in cooling mode (Comfort temperature)
°C
15.0
30.0
24.0
X
16412
201
Attenuation value on the room Set point in cooling mode
°C
1.0
10.0
6.0
X
16414
202
Room set point in heating mode (Comfort temperature)
°C
5.0
30.0
20.0
X
16413
203
Attenuation value on the room Set point in heating mode
°C
1.0
10.0
4.0
X
16415
204
Comfort / Attenuation conditions change:
On: Change Comfort / attenuation manually forced
Off: Mainteining the Comfort / Attenuation condition
-
Off
On
Off
X
16416
205
Beginning of the comfort conditions period:
Time of day when the transition to Comfort conditions is forced
h:
min
00:00
00:00
X
16465
206
End of period Comfort conditions:
Time of day when the transition to attenuation conditions is forced
h:
min
23:59
23:59
X
16466
207
Differential on the room temperature set point
Differential on the set temperature, in heating / cooling mode, with
which the heat pump is started
°C
1.0
5.0
1.0
S
16417
208
Active environment set point
°C
Read Value
8983
209
Voltage output status "Room Termostat" (clamps C-D):
On: Ambient temperature not satisfied: 230 V between terminals C-N
Off: Satisfied room temperature 230 V between terminals D-N
-
Read Value
8985
210
Winter climatic curve, minimum external environment temperature set
°C
-20.0
5.0
-5.0
S
16418
211
Winter climatic curve, minimum external environment temperature set
°C
10.0
40.0
20.0
S
16429
212
Winter climatic curve, minimum external environment temperature set
°C
10.0
60.0
22.0
S
16420
213
Winter climatic curve, minimum external environment temperature set
°C
20.0
60.0
45.0
S
16421
214
Factory parameter, do not change
-
-
-
0
S
16422
215
Winter climatic curve (fan coil), minimum water outlet temperature set
(active when remote contact "Set point 2" closed)
°C
20.0
60.0
45.0
S
16423
216
Winter climatic curve (fan coil), maximum water outlet temperature set
(active when remote contact "Set point 2" closed)
°C
10.0
60.0
45.0
S
16424
217
Summer climatic curve, minimum external environment temperature set
°C
20.0
40.0
23.0
S
16425
218
Summer climatic curve, minimum external environment temperature set
°C
20.0
40.0
32.0
S
16426
219
Summer climatic curve, minimum external environment temperature set
°C
6.5
25.0
15.0
S
16427
220
Summer climatic curve, minimum external environment temperature set
°C
6.5
25.0
22.0
S
16428
221
Factory parameter, do not change
-
-
-
0
S
16429
222
Summer climatic curve (fan coil), minimum water outlet temperature set
(active when remote contact "Set point 2" closed)
°C
6.5
25.0
7.0
S
16430
223
Summer climatic curve (fan coil), maximum water outlet temperature set
(active when remote contact "Set point 2" closed)
°C
6.5
25.0
7.0
S
16431
224
Maximum temperature of the hot water to the radiant system
°C
10.0
60.0
45.0
S
16432
225
Disabling the use of dew point temperature to calculate the minimum
limit of cold water to the radiant system:
On: As a minimum limit for cold water to the radiant system, the fixed
value is assumed“
” (par228)
Off: The dew point value is taken as the minimum limit of the cold water
to the radiant system“ “
” (par229)
-
On
Off
Off
S
16433
226
TDew temperature
If the CRONO-TH is not connected, or in case of alarms
co
_
read value is 0
°C
Read Value
S
8989
227
Offset between dew temperature and minimum cold water limit
to the radiant system :
To take into account the type of structure of the radiant system, the
minimum cold water temperature is given by the dew temperature plus
this value.
°C
-10.0
10.0
-2.0
S
16434
228
Value assumed, such as minimum temperature of the cold water to the
radiant system, if the dew point temperature is not available “
”
(par226) or is set to “
” (par225) = On.
°C
12.0
25.0
18.0
S
16435
229
Since the calculation: “
e
”(par226) + “
”(par227).
Value assumed, as the minimum temperature of the cold water to the
radiant system, if the dew temperature is available “
” (par226) and
is set to “
” (par225) = Off.
°C
Read Value
S
8990
230
Set point of the water leaving the heat pump for the air contioning:
Calculated through the climatic curve, taking into account dynamic
compensation, and temperature limits.
°C
Read Value
8991
X = Parametro disponibile anche sul CRONO-TH
S = Password service
7. LIST OF PARAMETERS "SMART MT"
Parameter List MIRAI-SMI - Menu parameter list "Prg" SW Vers.1.9.7