75
1. DESCRIZIONE DEI COMPONENTI
GB
GB
Make sure that the general power supply has been turned off. Never touch
the electrical components immediately after removing the power supply,
always wait at least 5 minutes .
• The electrical connections must be carried out by qualified personnel and in
compliance with the regulations in force in the place of installation
• The connection must be preceded by an accurate check of compatibility
between the power supply line and the characteristics to be connected.
• The unit must be connected to an impedance electrical network
≤
0,354
Ω
5.5 Electrical System
Connect the Earthing Cable
The earthing cable must not be connected to the piping, the
gas supply, lightening rods or telephone lines; incorrect earth-
ing can cause electrical discharge and damage to the unit.
Grounding wire
Power supply cable
Cable press
PCB TERMINAL BLOCK
TERMINAL
Fuse 10A
Internal
scheme
to the PCB
TERMINAL
BLOCK
A
1
2
3
4
5
6
Temp. Water
Supply System
Outdoor
Temp.
Sanitary Tank
Water Sensor
IN
COM
12V
7
8
9
Dew Point
Sensor
Remote
On/Off
10
11
Night
Mode
12
Remote
Cool/Heat
13
14
+
Set Point 2
-
Out Signal
0-10V
26
27
Power Supply
24V 3VA
C
D
E
Room
Thermostat
Elec. heat
Sanitary
Pump 1
L
K
J
F
Input
Pump1-2
Ext. Heat
Source
L
I
Out Pump 2
H
G
3W. V. Sanitary
Dehumidifier
-
+
G
12V
Sig.
GND
LAN
RS485
Model
Supply Cable (mm
2
)
Capacity of differential
magneto thermal switch
(A)
EH0618DC
2,5
16
EH1018DC
4
20
EH1218DC
4
25
EH1618DC
6
32
EH1718D3
2,5
16
WARNINGS
• Make sure to use a dedicated power supply only for the heat pump.
• The heat pump power cables must have a section equal to or greater
than that indicated in the following table.
• The power cord must comply with the IEC standard. (60245 IEC57
(H05RN-F)
• In the power supply line of the unit it is mandatory to provide a differ-
ential / magnetothermal switch with a contact separation of at least
3 mm in each pole, with a maximum trip threshold of 30 mA, sized
according to the table:
10 mm
30 mm
Magnetothermal /
Differential Switch
Distribution
Panel
L1 L2 L3
TERMINAL EH1718D3
Alimentation
Cable press
Ground Wire
5. INSTALLATION
By removing the cover of the electrical panel you have access
to the heat pump terminal board and to the PCB-TERMINAL BLOCK.
Summary of Contents for EH0618DC
Page 106: ...106 Note...
Page 107: ...107 Note...