4. WARNINGS
PHYSICAL AND CHEMICAL PROPERTIES
Information on main physical and chemical properties
Form
Gas
Form
Liquefed Gas
Colour
Colourless
Odour
Smell of ether
Boiling Point
-51,6 °C (101,325 kPa)
Relative Density
1,1 (Reference)
Solubility in water
280 g/l
STABILITY AND RECTIVITY
Chemical stability
Stable under normal conditions.
Incompatible Materials
Air and oxidizers. For material compatibility, see the latest version of ISO-1114.
Hazardous decomposition
products
Under normal conditions of storage and use, hazardous decomposition products should not be produced.
TOXICOLOGICAL INFORMATION
Acute toxicity by product
ingestion
Basing on the available data, classification criteria are not met.
Acute toxicity when the product
has skin contacts
Basing on the available data, classification criteria are not met.
Acute toxicity by product
inhalation
Difluoromethane - LC 0 (Rat, 4 h): > 520000 ppm Remark: Gas
ECOLOGICAL INFORMATION
Product bioaccumulative
potential:
The product is expected to be biodegradable and is not expected to persist for long periods in an aquatic
environment.
Product mobility in the ground:
Due to its high volatility, the product is unlikely to cause ground or water pollution.
DISPOSAL CONSIDERAZIONS
Waste treatment methods Gene-
ral Information:
Do not discharge into any place where its accumulation could be dangerous. Consult your supplier for specific
recommendations. Do not discharge it in areas where a risk of forming explosive atmospheres with the air exists.
The gas should be disposed of in a suitable burner with flash back arrestor
Disposal methods:
Refer to the EIGA code of practice (Doc. 30 "Disposal of gases", downloadable at Http://www.eiga.org) for better
guiding disposal methods
Contact your supplier for the proper disposal of the case. The discharge, treatment or disposal may be subject to
national, state or local regulations
The unit is designed to be installed outdoors. In the event of storage, comply with the following requirements:
The R32 is a flammable refrigerant gas with a low combustion speed.
The models EH1218DC, EH1618DC, EH1718D3 contain a quantity of refrigerant such that, in case of loss, to guarantee
that the concentration of gas in a room does not become dangerous, the following limits must be respected:
- for EH1218DC units located near the floor, the minimum area of the room is 42 m
2
;
- for wall-mounted EH1218DC units, the minimum area of the room is 6 m2 (height from the ground equal to 1.8 m);
- for units EH1618DC (or EH1718D3) placed near the floor, the minimum surface of the room is 67 m
2
;
- for wall-mounted units EH1618DC (or EH1718D3) the minimum surface of the room is 7 m2 (height from the ground equal to 1.8 m);
In addition, make sure that the calculated value below is lower than or equal to the toxicity limit to ensure that in case of loss the concentration of gas in the room
does not become dangerous (for R32 the limit concentration is equal to 0.3 kg / m
3
):
Total amount of refrigerant contained in the unit (kg) / volume of the room where the unit is installed (m3)
≤
0.3 kg / m