background image

The Ductless Split System of Choice

Made in Rome, New York, USA

9

The control board can be accessed by removing the

return air grill and control box cover with a flat blade screw-

driver or a nutdriver.

NOTE:

  The  microprocessor  will  read  the

dipswitch settings during power up. If the set-

tings need to be changed, disconnect the low

volt  power  to  the  evaporator  for  at  least  1

minute. In some cases this also means switch-

ing the power to the condenser off. Reapply

power for settings to take effect.

TROUBLESHOOTING WSP/WHP & FSP/FHP

UNIT  MOUNT  INFRARED  COMPATIBLE

CONTROL*

* When troubleshooting the WHP or FSP/FHP units, refer to the

wiring diagram on the back of the removeable return air grill. If

you are unable to locate this diagram, please call (315) 336-3716
and a copy can be faxed or mailed.

EMI 

AmericaSeries

 evaporators are designed to oper-

ate with EMI 

AmericaSeries

 condensers. Both the evapora-

tor (indoor unit) and condenser (outdoor unit) have a line

volt service connection and are intended to independently

connect to the electrical service panel (see the unit name

plate for the correct breaker type and size).

The indoor and outdoor units are also connected to

each other via 24v interconnect wiring. A transformer lo-

cated in the condensing unit provides the low volt power

source. The number of low volt conductors will be three to

five depending on heating options. Cooling only and cool-

ing with electric heat units have three (3) low volt wires

while heat pumps with electric heat have five.

C

OOLING

 O

NLY

 U

NITS

On cooling only units there are three low volt wires

on both the indoor and outdoor units. The yellow, red, and

brown wires of the air handler should be connected to the

corresponding yellow, red, and brown wires of the condenser.

A 24v transformer located in the condensing unit provides

low volt control power to both the air handler and condenser.

The 24v power supply can be measured across the red

(R) and brown (C) wires. The air handler will switch on and

off the condenser through the yellow (Y) wire. When the air

handler is calling for cooling, 24v can be measured between

terminals (wires) Y and C.

NOTE:

 Most condenser manufacturers do not

supply  low  volt  transformers  with  their

condensers.  When  connecting  an  EMI

evaporator  to  a  non-EMI  condenser,  a

transformer  may  have  to  be  added  to  the

system to provide 24v power.

C

OOLING

 O

NLY

 

WITH

 E

LECTRIC

 H

EAT

 U

NITS

Units  with  electric  heat  have  a  strip  heater  located

behind the evaporator coil. The control relay for the heater

in located on the circuit board in the control box. A limit

switch located on the heater end plate will interrupt power

to the heater should the airflow become compromised. If

temperatures rise above the limit setting a non-resetting one

time fuse link will burn and the heater will remain off.

The following current values apply when the unit is

connected to a 230v power supply. These values include fan

motor current:

3kw (13.5 amps)

4 kw (18 amps)

5kw (22.3 amps)

H

EAT

 P

UMP

 

WITH

 E

LECTRIC

 H

EAT

Heat pump units with electric heat have five intercon-

necting 

low volt

 wires on both the indoor and outdoor units.

The yellow, red, white, orange, and brown wires of the air

handler should be connected to the corresponding yellow,

red, white, orange, and brown wires of the condenser. A 24v

transformer located in the condensing unit provides low  volt

control power to both the air handler and condenser.

With high volt power supplied to the condenser, 24v

can be measured across the red (R) and brown (C) wires at

all times.

C

OOLING

The air handler will cycle the condenser on and off

through the yellow (Y) wire. To check for a condenser sig-

nal, place the indoor unit in cooling mode and choose a

setpoint temperature that is below room temperature. Then,

with a voltmeter, check for 24 volts across the yellow (Y)

and brown (C) wires.

EMI’s heat pump systems utilize a reversing valve is

that is energized in the cooling mode. The reversing-valve

signal is provided through the orange (O) low volt wire. It

will remain energized constantly as long as the unit remains

in cooling mode. To check for 24v reversing valve voltage,

place a voltmeter across the brown (C) and orange (O) wires

while the indoor unit is in the cooling mode.

Image of Dipswitch on Control Board

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: